Collins 516F-2 & S-Line
The Switched Neutral AC Power Design Defect
A comprehensive guide for operators worldwide: why the 516F-2 presents a live mains hazard when switched off, how mains voltage, plug polarity and wiring standards vary by country, and what corrective action is required to make the equipment safe to operate and service.
The defect described in this post means the Collins 516F-2 power supply has live mains voltage on its transformer primary wiring, fuse, and mains filter capacitors regardless of switch position, at any mains voltage on any continent. This is a design characteristic present in every production 516F-2 ever made, not a fault specific to any unit.
Do not open the 516F-2 chassis for any reason — including fuse replacement — without first removing the mains plug from the wall socket. The front-panel switch being OFF is not safe isolation under any mains voltage.
Section 1 — The Switched Neutral Defect
How the Collins S-Line Power System Works
The 516F-2 has no power switch of its own. It is controlled by the on/off switch in the associated transceiver or transmitter via specific pins of the 11-pin power cable. The front-panel switch interrupts the AC circuit, de-energising the 516F-2 transformer. The problem is which conductor is interrupted.
The single-pole power switch is connected in the neutral conductor of the mains circuit — confirmed in community discussion: “Even Collins did the switching of the neutral even up through the 516F-2.”1 Interrupting the neutral stops current from flowing, so the equipment is functionally off. But the active conductor remains permanently connected to the transformer primary, fuse, and all primary-side components, including the Y-class mains filter capacitors, at full mains voltage — at all times the mains plug is inserted.
SAFE DESIGN — switch in ACTIVE conductor:
Wall ──[ACTIVE]──[SWITCH]──── Transformer primary ──[NEUTRAL]── Wall
│
OFF: Active disconnected. Primary at 0V ✓
COLLINS 516F-2 — switch in NEUTRAL conductor:
Wall ──[ACTIVE]───────────── Transformer primary ──[SWITCH]──[NEUTRAL]── Wall
│ │
Always live OFF: current stops, but —
Active still on primary ✗ Fuse on neutral ✗
C15 (active→chassis) always energised ✗
Wire colours by region:
Australia/NZ: Active=brown/red Neutral=blue/black Earth=green/yellow
USA/Canada: Hot=black Neutral=white Ground=green/bare
UK: Line=brown Neutral=blue Earth=green/yellow
Europe/Schuko: Live=brown Neutral=blue Earth=green/yellow
Japan: Hot=black Neutral=white (often 2-pin only)
Brazil: Phase=brown/black Neutral=blue Earth=green/yellow
Figure 1. Switched-neutral architecture and wire colour conventions by region.
The Fuse Is Also on the Wrong Side
The 516F-2 mains fuse is on the neutral side — the same side as the switch. When the fuse blows, the transformer de-energises, but the active conductor is still connected to the fuse holder and all primary wiring. Opening the 516F-2 to replace a blown fuse while the mains plug is inserted means making contact with 230 V, 120 V, or whatever local mains voltage at the fuse holder. Always remove the mains plug before any work inside the 516F-2 — including fuse replacement.
Section 2 — Global Operations — Voltage, Plug Polarity & Wiring Standards by Region
Primary Winding Configuration — Confirm Before Connecting to Mains
115/120V OPERATION — primary windings IN PARALLEL: [Winding 1: green–green] PARALLEL [Winding 2: white–white] Combined impedance halved. Supply current: 4 A nominal. Remove capacitor C1 if line frequency > 60 Hz. 230V OPERATION — primary windings IN SERIES: [End of Winding 1] → [Start of Winding 2] (green to white junction) Combined impedance doubled. Supply current: 2 A nominal. Remove capacitor C1 if line frequency > 60 Hz. WRONG CONFIGURATION CONSEQUENCE: 115V winding on 230V mains → transformer core saturates → immediate overheating → failure. 230V winding on 115V mains → output voltages approximately halved → radio will not operate.
Figure 2. 516F-2 primary winding configuration — 115/120 V vs. 230 V.
Global Operations Reference Table
Region / Country |
Mains V AC |
Hz |
Plug type |
Polarised? |
Wiring standard |
Primary config |
Shock severity |
|---|---|---|---|---|---|---|---|
| Japan | 100 | 50 (east) / 60 (west) | Type A (NEMA-compatible) | Partial — newer outlets only | JIS C 8335 / IEC 60364 | Parallel — but 100 V is below design spec (see notes) | Still potentially fatal (100 mA at 1 kΩ) |
| United States / Canada | 120 (nominal; actual 115–126) | 60 | Type B (NEMA 5-15 / 5-20) | Yes — NEMA polarised plug (wide blade = neutral) | NEC (NFPA 70) / CEC | Parallel | Potentially fatal (120 mA at 1 kΩ) |
| Mexico / Central America | 127 (some areas 120) | 60 | Type A / B | Variable — not always enforced | NMX / local codes | Parallel | Potentially fatal |
| Brazil (part) | 127 (some cities) / 220 (others) | 60 | Type N (NBR 14136) — 3-pin | Yes — Type N is polarised | NBR 5410 | Parallel (127 V) or Series (220 V) — verify by city | Potentially fatal at both voltages |
| Australia / New Zealand | 230 | 50 | Type I (AS/NZS 3112) — angled flat 3-pin | Partial — newer GPOs polarised; older may not be | AS/NZS 3000 | Series | Highly dangerous (~230 mA at 1 kΩ) |
| United Kingdom / Ireland | 230 | 50 | Type G (BS 1363) — rectangular 3-pin, fused | Yes — BS 1363 polarised; Line = narrower pin | BS 7671 (IET 18th Edition) | Series | Highly dangerous |
| Continental Europe (Schuko) | 230 | 50 | Type F (CEE 7/4 Schuko) — round 2-pin + earth clips | No — Schuko is non-polarised. Either orientation is possible. | IEC 60364 / HD 60364 / national codes | Series | Highly dangerous |
| France / Belgium (Type E) | 230 | 50 | Type E (CEE 7/5) — round 2-pin + earth hole | No — non-polarised | NFC 15-100 / IEC 60364 | Series | Highly dangerous |
| India / Pakistan / parts of SE Asia | 230 | 50 | Type D / Type M (BS 546 large round) | Yes — large earth pin enforces orientation | IS 732 / NBC India / BS 7671 | Series | Highly dangerous |
| South Africa / Namibia / Zimbabwe | 230 | 50 | Type M (BS 546 large round 3-pin) | Yes — earth pin orientation enforced | SANS 10142 | Series | Highly dangerous |
| Singapore / Malaysia / Hong Kong | 230 | 50 | Type G (BS 1363) | Yes — same as UK | SS 638 / MS IEC 60364 / HKIE code | Series | Highly dangerous |
| China / Taiwan | 220 (China) / 110 (Taiwan) | 50 (China) / 60 (Taiwan) | Type A (Taiwan) / Type A or I (China) | Variable — modern outlets partially polarised | GB 16895 (China) / CNS 690 (Taiwan) | Series (China 220V) / Parallel (Taiwan 110V) | Highly dangerous (China) / Potentially fatal (Taiwan) |
| Israel | 230 | 50 | Type H (SI 32) — V-shaped 3-pin, or Type C | Yes — Type H is polarised | Israeli standard SI 900 | Series | Highly dangerous |
| Switzerland | 230 | 50 | Type J (SEV 1011) — 3 round pins | Yes — Type J has earthed orientation pin | NIV / SEV 1000 | Series | Highly dangerous |
Detailed Notes by Region
Japan (100 V / 50 or 60 Hz)
Japan is the only country in the world using 100 V as its standard residential mains voltage. The 516F-2’s two primary windings, connected in parallel, are designed for 115 V — operating them at 100 V means the transformer is under-driven by approximately 13%. The secondary voltages will be proportionally lower: LV B+ will be approximately 240 V instead of the specified 275 V, and HV B+ will be approximately 695 V instead of 800 V. The radio will function, but PA output power will be reduced and the bias supply may fall outside its adjustment range. A step-up autotransformer (100 V to 115 V, 500 W minimum) is recommended for Japanese operation.
Regarding the switched-neutral defect: older Japanese outlets (Type A, non-polarised) do not enforce plug orientation, making the switched conductor unpredictable. Newer Japanese outlets are polarised, with the wider slot connected to neutral — identical to the US NEMA convention. Even at 100 V, the shock current through wet skin (1 kΩ) is 100 mA — right at the fibrillation threshold. Japan’s 100 V mains should not be considered safe. The same rules apply: unplug before opening.
United States and Canada (120 V / 60 Hz)
Factory configuration. The NEMA 5-15 polarised plug (wide blade = neutral, narrow blade = hot) provides consistent polarity at correctly wired US outlets — the Collins design relies on this. In a correctly wired and correctly polarised installation, the neutral is reliably switched. However, the active conductor is still permanently connected to the primary, and the defect remains. Non-polarised extension cords, old reversed sockets, and non-polarised adapters all invalidate the polarity assumption.
Modern US mains voltage typically measures 120–126 V rather than the original 115 V design basis. This elevated voltage increases B+ outputs above specification. With tube rectifiers, unloaded LV B+ can exceed 310–360 V at 120 V mains. The Weber K5IU article in The Signal documents these measurements in detail and their effect on aging component stress.3
Brazil (127 V or 220 V depending on city)
Brazil is unique in using two different residential voltages — 127 V in São Paulo, Rio de Janeiro, and parts of the south, and 220 V in Brasília, Belo Horizonte, and the northeast. A 516F-2 operated in Brazil requires voltage verification before connection. The primary wiring must be in parallel for 127 V cities and in series for 220 V cities. The Type N (NBR 14136) plug used since 2011 is polarised, but older Type A or C outlets (still common) are not. Verify the outlet type and polarity before connecting.
United Kingdom and Ireland (230 V / 50 Hz)
The BS 1363 Type G plug provides the best plug-level safety of any region. The plug contains a fuse (typically 3 A or 5 A for low-load equipment) that blows before the mains wiring is overloaded. The plug is polarised — the rectangular Live pin is distinguishable from the Neutral pin by position, and the Earth pin is longer (it opens the socket shutters). The socket is always wired: Live = top-right, Neutral = top-left, Earth = top-centre. UK wiring (BS 7671) requires that single-pole switches interrupt the Line (live) conductor.
Despite the superior plug safety, the switched-neutral defect is fully present once the mains lead enters the 516F-2 chassis. The BS 1363 plug fuse protects the mains lead; it does not protect against the primary-side live conductor being present when the radio appears off.
Continental Europe — Schuko and Type E (230 V / 50 Hz)
This is the most hazardous plug configuration for the switched-neutral defect. The Schuko (CEE 7/4) and Type E (CEE 7/5) plugs are completely non-polarised. Either orientation of the plug in the socket is equally valid, meaning there is no reliable way to predict which of the two mains conductors (Live or Neutral) is connected to which pole of the 516F-2 mains lead. The Collins design assumed the neutral would be consistently on the switched side — this assumption is entirely invalid in Schuko installations.
In any given Schuko installation, the 516F-2 front-panel switch may be breaking either the Live or the Neutral conductor, determined by whichever orientation the mains plug was last inserted. Rotating the plug in the socket reverses the polarity. The switched-neutral defect in a Schuko country is therefore not merely a fixed design limitation — it is a random hazard that changes each time the plug is removed and reinserted.
India, South Africa, Singapore, UK-derived Standards (230 V / 50 Hz)
Countries using BS 1363 (UK, Singapore, Malaysia, Hong Kong, Pakistan, some of the Middle East) or BS 546 variants (India, South Africa, Zimbabwe, Namibia) have polarised plugs with defined Live and Neutral positions. The wiring standards in these countries (IS 732 India, SANS 10142 South Africa, SS 638 Singapore) all require single-pole switches to interrupt the Line conductor. The Collins design does not comply. The same remediation applies as for Australia — the rear-panel double-pole switch or full primary rewire.
Shock Severity — Quantitative Comparison by Voltage
Mains voltage |
Current at dry skin (100 kΩ) |
Current at wet skin (1 kΩ) |
Likely outcome at wet skin |
Notes |
|---|---|---|---|---|
| 100 V (Japan) | 1 mA | 100 mA | At fibrillation threshold | 100 mA is the approximate threshold for ventricular fibrillation. Japan’s 100 V is not safe. |
| 120 V (US/Canada) | 1.2 mA | 120 mA | Above fibrillation threshold — potentially fatal | 120 V provides more current than the fibrillation threshold through wet skin. |
| 127 V (Brazil/some regions) | 1.3 mA | 127 mA | Above fibrillation threshold — potentially fatal | Similar risk profile to 120 V. |
| 230 V (Australia/UK/Europe) | 2.3 mA | 230 mA | Well above fibrillation threshold — high likelihood of fatality | Energy approximately 4× greater than 120 V. Cardiac arrest is a likely outcome without immediate CPR and defibrillation. |
Section 3 — Safety Capacitor Replacement (C15 & C16) — All Regions
Why C15 Is Permanently Energised at All Voltages
C15 connects from the active/hot/live/Line conductor to chassis ground. Because the Collins switched-neutral design leaves the active conductor permanently connected to the primary wiring (regardless of switch position or mains voltage), C15 is permanently energised at full local mains voltage from the moment the mains plug is inserted until it is removed. This is true at 100 V, 120 V, 127 V, and 230 V equally. At 230 V (Australian/UK/European mains) the risk is greatest, but at no voltage is it acceptable.
Y2 Certification — Required Everywhere, Non-Negotiable
Y2-certified capacitors (IEC 60384-14) are engineered to fail open-circuit rather than short-circuit. This is the only acceptable replacement for C15 and C16 at any mains voltage. The Y2 rating includes an AC working voltage specification of 250 VAC, which provides adequate margin above all operating voltages worldwide including 230 V.
Capacitor Positions and Replacement Parts
Ref. |
Position / Risk |
Original value |
Required replacement |
Recommended part (worldwide) |
|---|---|---|---|---|
| C15 | Active conductor to chassis — permanently energised. Highest priority. | 10 nF (0.01 µF) ceramic disc | Y2, IEC 60384-14, 250 VAC minimum — adequate for all world voltages including 230 V | Kemet PHE840MY6100MR17 EPCOS/TDK B32021A3103M Vishay VY2102M63Y5US63V0 |
| C16 | Neutral conductor to chassis — energised when switch is ON | 10 nF ceramic disc | Y2, IEC 60384-14, 250 VAC minimum | Same as C15 — fit identical parts to both positions |
| C? (X-class) | Active to Neutral (line-to-line) — if fitted | 47 nF or 100 nF — verify against manual | X2, IEC 60384-14, 275 VAC minimum | Kemet PHE840MD6470MR06 (47 nF) EPCOS B32922C3104K (100 nF) |
Global Suppliers
Supplier |
Ships to |
Notes |
|---|---|---|
| Element14 / Farnell AU | Australia, NZ, Pacific | Next-day despatch from Sydney/Melbourne. Stocks Kemet PHE840 and EPCOS B32021 series. |
| Mouser Electronics | Worldwide (170+ countries) | Ships to US, EU, UK, Japan, Asia, South Africa, Brazil, India. Full Y2 and X2 range stocked. |
| Digi-Key | Worldwide | Comprehensive Y2/X2 range. Multiple Kemet, EPCOS, Vishay options. |
| RS Components (UK/Europe) | UK, EU, South Africa, India, SE Asia | Farnell-equivalent in Europe. Stocks Vishay VY2 series and EPCOS B32021. Same-day despatch from UK. |
| Farnell (UK/Europe/Americas) | Worldwide | Part of the element14 group. European stocking location for Kemet PHE840 series. |
Section 4 — Why Collins Used This Design
The switched-neutral design was common in American commercial and consumer electronics through the 1950s and 1960s. Several factors contributed:
- Single-pole switch economy. Running one switched conductor through the 11-pin power cable required only one switched line. With the US polarised plug enforcing consistent polarity, the neutral would predictably always be on the switched side.
- US wiring conventions of the era. The concept that single-pole switches must interrupt the active/hot conductor was not codified in the NEC until later editions. Switching the neutral was accepted 1950s American industrial practice and Collins was not unusual in adopting it.
- Polarised plugs as mitigation. The US NEMA polarised plug provided partial predictability in the intended operating environment. Collins engineers did not design for worldwide operation with non-polarised Schuko outlets or higher-voltage mains systems.
None of this changes the hazard the design creates for operators operating the equipment outside its original design environment, or who open it for service without understanding which conductors remain live.
Section 5 — Mains Wiring Best Practices — What Good Design Requires
The following principles define correct mains wiring practice and should be applied when modifying the 516F-2 mains input or adding isolation hardware:
Section 6 — Corrective Action — Four Levels
-
1
Procedural — remove the mains plug before opening the chassis. Always. The only action that removes the active conductor from the 516F-2 interior is physically pulling the mains plug from the wall. This applies at 100 V, 120 V, 127 V, and 230 V, with polarised or non-polarised plugs, in every country. Affix a reminder label to the 516F-2 front panel in your language: “Remove mains plug before opening — switch OFF does NOT isolate.”
-
2
Replace C15 and C16 with Y2-certified capacitors — do this first, regardless of other work Source from Element14, Mouser, Digi-Key, RS Components, or Farnell. Part: Kemet PHE840MY6100MR17 or EPCOS B32021A3103M. Cost: under the equivalent of AU$10 / US$6 / £5 / €6. Time: 30 minutes. Replace the X-class line-to-line cap at the same time. Verify values from the service manual before ordering.
-
3
Add a rear-panel double-pole mains isolation switch — strongly recommended for all regions; essential for Schuko countries Retrofit the 516F-2 with an IEC C14 panel-mount combined inlet and double-pole switch. When the rear switch is OFF, both active and neutral conductors are interrupted simultaneously — eliminating both the switched-neutral risk and the polarity-uncertainty risk in non-polarised outlet countries. Recommended part: Schurter DD11 series (IEC C14 inlet + double-pole switch + fuse, one panel cutout). Available from Element14, Mouser, Digi-Key, and RS Components worldwide. This modification involves mains wiring — comply with your local electrical wiring regulations and have the work checked by a licensed electrician.
-
4
Full primary rewire — switch the active conductor, relocate the fuse to the active side Rewire the 516F-2 internal primary circuit so the front-panel switch interrupts the active conductor and the fuse is on the active side. This brings the design into compliance with NEC, AS/NZS 3000, BS 7671, IEC 60364, and all other major wiring standards. The W0IY Service Bulletin 1 PCB kit implements this correction as part of a complete service update. Documentation: github.com/w0iy/516F-2. For operators not undertaking a full SB-1 upgrade, the rewire can be performed independently using the service manual schematic to identify the switched conductor path. All mains wiring must comply with local regulations.
Region-Specific Recommendations Summary
Region |
Minimum action |
Recommended action |
Additional notes |
|---|---|---|---|
| Australia / NZ | Level 1 + Level 2 | Level 1–4 | AS/NZS 3000 compliance requires Level 4. 230 V increases urgency of all measures. |
| US / Canada | Level 1 + Level 2 | Level 1–3 | Polarised plug provides partial mitigation. Verify socket polarity before use. |
| UK / Ireland | Level 1 + Level 2 | Level 1–4 | BS 7671 compliance requires Level 4. BS 1363 fused plug provides lead protection but not chassis isolation. |
| Schuko countries (EU, Russia, Korea etc.) | Level 1 + Level 2 | Level 1–4; Level 3 essential | Non-polarised plug makes switched conductor unpredictable. Level 3 double-pole switch is particularly important here. |
| Japan | Level 1 + Level 2 | Level 1–3 + step-up transformer | Use step-up transformer (100 V to 115 V). Verify outlet polarity — older outlets non-polarised. |
| Brazil | Level 1 + Level 2 | Level 1–3 | Verify city voltage (127 V or 220 V) and configure primary wiring before connection. Type N outlets (2011+) are polarised; older Type A/C are not. |
| India / South Africa / SE Asia | Level 1 + Level 2 | Level 1–4 | BS 546 / BS 1363 plugs are polarised. Local wiring standards require active switching. Level 4 brings the unit into compliance. |
Section 7 — Affected Equipment
Equipment |
Role |
Switch location |
Notes |
|---|---|---|---|
| Collins 516F-2 | AC power supply — no own switch | Controlled via 11-pin power cable | Contains transformer primary, fuse, C15/C16. Always de-energise at the mains plug. |
| Collins KWM-2 / KWM-2A | SSB/CW transceiver — contains the switch | Front-panel combined switch/volume pot | Switch controls neutral through the power cable. 516F-2 primary remains live on active side. |
| Collins 32S-1 / 32S-3 / 32S-3A | SSB transmitter — contains the switch | Front-panel switch | Identical architecture. Identical hazard. Identical remediation. |
| Collins 75S-3 / 75S-3B / 75S-3C | SSB receiver | Front-panel switch | Powered from the 516F-2 via station wiring. Switched-neutral applies to the shared primary. |
| Collins 312B-4 / 312B-5 | Station console / external PTO | No independent power switch | Powered from 516F-2 accessories output. Downstream of the defective supply. |
References & Citations
- [email protected], “Fuse/Switching of AC Neutral” (February 2022). Gary Follett W0DVN: “Even Collins did the switching of the neutral even up through the 516F-2 so someone must have thought it was a good idea.” groups.io/g/heathkit/topic/89410140. ↩
- Collins Collectors Association, CCA groups.io reflector, message 18005: groups.io/g/cca/message/18005. The community discussion that prompted this post. CCA membership required for access.
- Dick Weber K5IU, “A Look at the Low Voltage Section of the 516F-2 Power Supply and Related Issues” (2018), The Signal, Collins Collectors Association. Documents measured B+ output voltages across multiple 516F-2 configurations and line voltages. Available at: collinsradio.org — Weber 516F-2 PDF. ↩
- Collins 516F-2 Service Manual (9th edition, July 1974). Primary winding configuration documented in Section 1. Specification: “As supplied, the 516F-2 is factory-wired for 115-volt operation. Input: 115 or 230 volts, 50 to 400 Hz, 4 or 2 amperes.” Available via CCA: collinsradio.org/archives/manuals/.
- Barry Buelow W0IY, Collins 516F-2 Service Bulletin 1 PCB Kit. github.com/w0iy/516F-2 and Radio Farm Projects 516F-2. The SB-1 kit addresses the primary rewire and capacitor replacement comprehensively.
- IEC 60384-14: Fixed capacitors for use in electronic equipment — Part 14: Sectional specification for fixed capacitors for electromagnetic interference suppression and connection to the supply mains. Defines Y2 and X2 safety class ratings. iec.ch.
- IEC 60479-1: Effects of current on human beings and livestock — Part 1: General aspects. Defines the body current effect table including the 100 mA ventricular fibrillation threshold. iec.ch.
- National Electrical Code (NEC), NFPA 70. Article 404 (Switches): requires single-pole switches to interrupt the ungrounded (hot) conductor. nfpa.org.
- Standards Australia, AS/NZS 3000:2018 Wiring Rules. Section 4.4 requires single-pole switches to interrupt the active conductor. saiglobal.com.
- IET, BS 7671:2018 Requirements for Electrical Installations (18th Edition). Regulation 537.2 specifies isolation and switching requirements for UK/EU installations. electrical.theiet.org.
- Schurter DD11 series IEC inlet + double-pole switch + fuse module: search Schurter 6100.4155 at Element14 AU, Mouser, or RS Components.
- World Standards EU, “Plug, socket and voltage by country”: worldstandards.eu. Comprehensive reference for mains voltage, frequency, and plug types worldwide.
- Companion post on this site: “Collins KWM-2/KWM-2A Vietnam Modification (SCED 11b)” — Section 2b covers the full Y2 safety capacitor procedure with part numbers and installation notes: vk6ada.com.au.