Emtron DX-2 Linear Amplifier:
Restoration & Service Guide
GU84B (4CX2500A) Tetrode • 27 V Heater • 1,500 W Carrier / 7 Bands • Ferrite Toroid “L” Coil • Two-Speed Blower • Ig2+/Ig2− Screen Current Metering • RF Sub-Chassis • 9-Way Connector • Emona Electronics Sydney
The DX-2 operates at 2,500 V DC plate voltage — almost exactly the peak of a 120 V mains cycle multiplied by ten, or slightly above the peak of a 230 V mains cycle. The Emtron manual states: “The high voltages present inside the DX-2 are EXTREMELY DANGEROUS. Do not remove the top cover under any circumstances if any leads are still plugged into the rear of the amplifier — especially if the AC lead is plugged into the power outlet.”
- Disconnect ALL rear-panel leads before cover removal.
- Allow at least 5 minutes after power removal. Momentarily short the tube anode to chassis with an insulated discharge probe. Verify discharge with a 4,000 V-rated DMM before touching any internal component.
- The GU84B has a significantly larger tube mass than the GU74B and stores more thermal energy; allow additional time for the anode to cool before working near the tube area.
- The cover safety microswitch is the primary interlock; never defeat it.
1. DX-2 in the Emtron Product Line & Distinctions from the DX-1 Series
The DX-2 occupies the middle tier of the Emtron single-tube lineup: above the 750 W DX-1 series and below the DX-3 (3,000 W). The DX-2’s single GU84B tube is a substantial step up from the GU74B used in DX-1 models, reflecting the fundamental engineering challenge of delivering 1,500 W from a desktop amplifier: the GU74B can dissipate 800 W; the GU84B can dissipate 2,500 W, giving a 3:1 margin over the DX-1D at the same output power level.
The DX-2’s band coverage of seven bands (160–15 m) is a key service consideration. The omission of 12 m and 10 m was an engineering decision: at 1,500 W output into the higher HF bands, the GU84B’s larger inter-electrode capacitances and the physically large tank circuit required for 2,500 W tube operation create challenges at 21 MHz and above. The later DX-2SP solved this with an upgraded tank circuit, but the original DX-2 design was specifically rated for 15 m as the highest band.1
Parameter |
DX-1D |
DX-2 |
|---|---|---|
| Final tube | GU74B / 4CX800A; 800 W plate dissipation | GU84B / 4CX2500A; 2,500 W plate dissipation |
| Heater | 12.6 V / 3.5–4.0 A | 27 V nominal / 3.7 A (limits: 25.6–28.4 V) |
| Plate voltage | ~2,600 V DC | 2,500 V DC |
| Output power | 750 W average / 1,000 W PEP | 1,500 W carrier; 100% duty cycle |
| Band coverage | 9 bands (160m–10m, WARC included) | 7 bands (160m–15m only; no 12m or 10m) |
| L-coil (low bands) | Wound inductor on ceramic bobbin | Wound on ferrite toroid (unique in DX range) |
| Blower | Single-speed turbine | Two-speed turbine; speed controlled by temperature sensor |
| Temperature sensors | One sensor above tube | Two sensors above tube; horizontal orientation critical |
| Anode clamping diodes | 4× A106 in RF module | 7× A106 in RF module |
| Screen MOV protection | Not shown in DX-1D schematic | 275 V MOV in screen circuit (RF module schematic) |
| Screen current metering | Not separately displayed | Ig2+ and Ig2− both displayed on Display Board |
| AMPC board orientation | Vertical | Vertical (same direction; clockwise = more sensitivity) |
| Weight | ~20 kg | Heavier due to larger transformer; caution when handling |
| Output Power | 1,500 W carrier; 100% duty cycle; all supported bands |
| Frequency Coverage | 7 bands: 160, 80, 40, 20, 17, 15, and 30 m (does not cover 12 m or 10 m) |
| Final Tube | GU84B (= 4CX2500A, Svetlana St. Petersburg); single tetrode; 2,500 W plate dissipation; ceramic-metal; forced air cooled |
| Heater Voltage | 27 V nominal (limits: 25.6–28.4 V); current 3.7 A nominal (3.4–4.0 A); 3-minute minimum warm-up |
| Plate Voltage | 2,500 V DC (nominal as per Emtron manual) |
| Screen Voltage (G2) | Regulated; measured at EG2 (blue wire); GU84B rated to 400 V max G2 |
| EBS Standing Current | ~0.3–0.4 A (confirmed from Emtron DX-2 manual: plate current jumps to 0.3–0.4 A when 0.5–1 W of drive is applied) |
| RF Sub-Chassis | Separate; GU84B tube positioned on RF sub-chassis; 9-way heavy-duty connector; all connections except plate under sub-chassis |
| L Coil (low bands) | Wound on ferrite toroid (unique to DX-2/DX-4); provides 40–160 m low-band inductance |
| Pi Coil (high bands) | Silver-plated copper tube coil for higher HF bands (approx. 15–20 m range) |
| Blower | Two-speed commercial turbine; speed controlled by temperature sensor; higher speed activates with increasing tube temperature |
| Temperature Sensors | Two sensors above tube; must remain near-horizontal; high voltage between sensors and tube anode |
| Band Switch | 9-position ceramic switch (supporting 7 active bands plus positions for 2 additional settings); silver-plated contacts |
| Tune/Load | Two variable capacitors; 6:1 reduction drive both axes; factory initial settings table on manual page 2 |
| Control Board | AMPC v.3.x; vertically mounted; clockwise pot rotation = increased sensitivity (same as DX-1) |
| Display Board | LM3914 bar-graph ICs; Ip, Vp, forward power, reflected power, Ig2+ and Ig2− screen current metering |
| T/R Switching | Standard antenna relay; optional Jennings TJ1A-26S QSK vacuum relay module |
| Soft Start | TRIAC-based; TDA1085C controller; 5-second ramp (longer than DX-1D’s 3 seconds); X2 and Y2 safety capacitors |
| Protection | Plate current (IPTRIP/POT6); screen current Ig2LIMIT (POT1); screen voltage (POT2/SCREEN); overdrive; SWR; temperature; mains interlock |
| Mains | 200–240 VAC only (DX-2 should not be connected to less than 200 VAC per manual); transformer rewire for different voltages |
| Cabinet | 2 mm steel; dark yellow chromate coating; 3 mm anodised aluminium front panel; baked enamel texture finish |
| Manufacturer | Emtron Division of Emona Electronics Pty Ltd; 92–94 Wentworth Ave, Sydney NSW 2010, Australia |
2. Pre-Service Assessment
2.1 Mains Voltage Requirement
The DX-2 manual contains a specific warning not found in any DX-1 documentation: “The DX-2 should not be connected to a mains supply of less than 200 VAC.” The DX-2’s larger transformer and higher power requirements make it incompatible with 100–120 VAC operation without transformer modification — unlike the DX-1 series which supports 100/120 VAC with derating. The transformer supports 200, 220, 230, and 240 VAC configurations; verify the correct tap is connected before any power-on on a used DX-2.
2.2 Initial Diagnostic Checklist
- READY LED not activating: C7 (22 μF tantalum) timer capacitor failure is the primary suspect; same diagnosis as all DX-1 models.
- Low plate voltage: TDA1085C soft-start controller failure (measure Vcc at pin 9; expect ~15.6 V); DX-2 soft-start is a 5-second ramp (vs DX-1D’s 3 seconds).
- Blower operating at only one speed: temperature sensor or two-speed motor control circuit fault. Verify both temperature sensors are intact and positioned correctly (near horizontal).
- Excessive idle plate current: EBS jumper loss on solder side of AMPC board; check before any bias adjustment.
- No output despite correct plate voltage: Screen supply failure; measure at EG2 (blue wire). The DX-2 adds an additional SCREEN VOLTAGE adjustment (POT2) not present in DX-1D; verify screen voltage is within specification before tube investigation.
- Ig2+ or Ig2− bargraph showing constantly high reading: Screen current limit circuit fault on AMPC board; verify POT1/IG2LIMIT setting.
- Power output dropping steadily over time: GU84B cathode emission fatigue. The manual notes tube replacement is very unlikely, but long-service tubes do age. The GU84B has a designed life of 1,500 hours.
2.3 Required Test Equipment
- High-voltage DMM, minimum 4,000 V DC range
- Standard DMM for low-voltage, resistance, and diode measurements
- RF wattmeter, 1.5–22 MHz, 2,000 W range (Bird 43 or equivalent)
- 50 Ω dummy load rated 1,500 W continuous
- Adjustable DC current source, 0–2 A, for IPTRIP adjustment via TP2
- Insulated HV discharge probe (10 kΩ / 25 W; chassis clip lead)
3. GU84B (4CX2500A) Tetrode — Service & Heater Circuit
3.1 GU84B Tube Characteristics
The GU84B is a Svetlana (St. Petersburg, Russia) ceramic-metal forced-air-cooled tetrode designed primarily for submarine and military radio transmitters. Emtron described it as “constructed primarily for military communication, this tube is physically and electrically exceptionally rugged.” Its 2,500 W plate dissipation and exceptional mechanical robustness made it ideal for the DX-2’s 1,500 W output requirements, operating with a comfortable margin at approximately 60% of maximum plate dissipation in normal Class AB1 service.
The GU84B’s most distinctive service characteristic, compared to the GU74B in DX-1 models, is its 27 V heater (nominal), drawing 3.7 A. This is an unusual heater voltage that requires a dedicated secondary winding on the DX-2 transformer. An incorrect heater voltage will either damage the cathode (too high) or reduce emission (too low) with potential cathode contamination over time from under-temperature operation.2
3.2 NOS GU84B Conditioning (Gettering)
Replacement GU84B tubes are available primarily as new-old-stock (NOS) from Russian military surplus, from Svetlana factory stocks held in European warehouses. Like the GU74B, a NOS GU84B requires gettering before plate voltage is applied: a minimum of 8–15 hours with heater voltage only (no G1, no G2, no plate) to drive out adsorbed gas molecules. The GU84B’s larger physical mass and greater anode surface area means the gettering process may take longer than for the GU74B; conservative practice is to run the heater at full rated voltage for 12–16 hours before progressive application of plate voltage.
Item & Description |
Service Notes |
|---|---|
V1 (GU84B / 4CX2500A)
Final amplifier tube
GU84B; 2,500 W plate dissipation; 27 V / 3.7 A heater; ceramic-metal; 2,200 V max anode; operated at 2,500 V in DX-2
|
Sources: Svetlana NOS from Russian military surplus — DL3JJ / QRO-Shop (qro-shop.com); RF Parts Co. (rfparts.com); Soviet-Tubes.com. After installation, the BIAS (POT3) and PRE-BIAS (POT7) adjustments are required. The manual states: “It is very unlikely that you will ever need to replace the GU84B.” The tube is extremely robust and long-lived under normal conditions; replacement is typically prompted only by vacuum failure (getter whitening) or cathode emission loss after extended service exceeding the 1,500-hour rated life. Verify getter condition (bright silver-metallic appearance) before concluding the tube has failed. |
TUBE SOCKET
GU84B (4CX2500A) ceramic tube socket
Standard 4CX2500A base; filament/cathode/G1/G2/plate contacts; forced-air plenum below socket
|
Inspect for arc damage, cracked ceramic, and contact spring fatigue. The 27 V heater contacts must carry 3.7 A continuously; inspect for signs of heating from high-resistance contacts. The G2 (screen) contact carries higher voltage than in DX-1 models; inspect carefully. Clean all contacts with isopropyl alcohol; verify contact spring tensions. The forced-air plenum below the socket must seal correctly for the blower to direct air through the tube anode fins. |
TWO TEMPERATURE SENSORS
Dual thermal sensors above tube anode
Both must be near-horizontal; HIGH VOLTAGE between sensors and anode; control two-speed blower
|
The DX-2 uses two temperature sensors above the GU84B tube, one primary and one for redundancy or dual-threshold switching. The DX-2 manual includes the same warning as the DX-4 manual: “The sensors must stay in a position close to horizontal. Make sure you are not pushing them down, too close to the tube, as high voltage exists between them.” After any tube service, verify both sensors are repositioned correctly. A sensor pushed down toward the tube body creates a dangerous flashover path from the anode to the sensor mounting. The two-speed blower control relies on these sensors; verify correct speed switching after any temperature sensor service. |
TWO-SPEED BLOWER
Two-speed commercial turbine blower
Temperature-sensor controlled; low speed at start-up; higher speed activated by thermal sensor at elevated tube temperature
|
Unlike the single-speed blower in the DX-1D, the DX-2 blower has two operating speeds. The motor should be verified on both speeds: at cold start, the lower speed should run; after sustained high-power operation, the higher speed must engage. A blower motor that runs at only one speed (stuck on low or stuck on high) indicates a failed motor speed-change contact or a faulty temperature sensor. At maximum plate power, the cooling airflow must be adequate for the 2,500 W dissipation capability of the GU84B. A blower that does not run at all must be replaced before any power-on; the GU84B will overheat within seconds at full power without forced-air cooling. Clean the blower annually with compressed air. |
9-WAY SUB-CHASSIS CONNECTOR
RF sub-chassis to main chassis interconnect
Same architecture as DX-1D; carries heater (27 V), G1 bias, G2 screen, cathode connections
|
Inspect all contact spring tensions and look for thermal discolouration. At 27 V / 3.7 A for the heater, the heater contacts carry higher current than in DX-1 models (GU74B heater was 12.6 V / 3.5 A). High-resistance heater contacts will cause the heater voltage to drop below the specified 27 V nominal at the tube socket, leading to under-emission and shortened tube life. Verify the heater voltage at the tube socket pins with a DMM; it should read within 25.6–28.4 V. |
4. RF Deck — Ferrite Toroid L-Coil & Pi-Network
4.1 Ferrite Toroid “L” Coil — Unique to DX-2 and DX-4
The most distinctive RF circuit feature of the DX-2 (shared with the DX-4 but absent in the DX-1 series and DX-3) is the use of a ferrite toroid as the low-band “L” coil in the pi-L output network. The DX-2 manual states: “Next to the switch is the ‘Pi’ coil. The ‘L’ coil is wound on a ferrite torroid.” The pi-L network uses the Pi coil (silver-plated copper tube) for the primary tank inductor and the ferrite toroid L-coil as the low-impedance secondary element providing the final 50 Ω output impedance transformation at the lower frequency bands (approximately 40–160 m).3
The ferrite toroid coil is a high-Q, compact inductor that allows the pi-L network to maintain good loaded-Q even at 160 m where the required output inductance is very large. At higher frequencies (15–20 m), the L-coil may be effectively bypassed or its contribution minimised by the band switch configuration. Service considerations for the ferrite toroid are distinct from service of wound wire coils on ceramic bobbins (as used in the DX-1D) because ferrite cores are susceptible to cracking from thermal cycling and can be permanently demagnetised by temperature extremes or mechanical shock.
Component & Description |
Service Notes |
|---|---|
L-COIL (ferrite toroid)
Low-band (40–160 m) ferrite toroid “L” coil
Wound on ferrite toroid; pi-L network secondary element; unique to DX-2 and DX-4 in the Emtron range
|
Inspect the ferrite toroid core for cracking, chipping, or discolouration from overheating. A cracked toroid does not always cause immediate failure but will change its permeability and shift the resonant frequency of the band it supports. A failed or incorrectly-wound toroid L-coil typically manifests as inability to achieve correct tune/load settings on the lower HF bands (40m, 80m, 160m), excessive tune or load capacitor settings at those bands, or asymmetric power output on the affected bands.
Ferrite core service precautions: Do not drop or mechanically shock the toroid coil assembly. Do not operate the amplifier at high power with the tank compartment open, as the RF field around the toroid can induce heating in nearby metal objects. Clean the toroid winding with isopropyl alcohol only; do not use solvents that may attack ferrite core coatings. If the core appears intact but performance is degraded on low bands, measure the L-coil inductance with an LC meter or network analyser (with the coil disconnected from the circuit) and compare to the DX-2 factory specification. Contact Dan at emtrondv.com for the correct inductance specification. |
PI COIL (silver-plated copper tube)
High-band (15–20 m) pi-network primary coil
Silver-plated large-diameter copper tube; same construction as DX-1D pi-coil but sized for DX-2 power level
|
Inspect the silver-plated copper tube coil for arc damage, tarnished silver plating, and physical distortion. At 1,500 W, the RF circulating current in the pi-coil is substantially higher than in the DX-1D. Minor tarnish on the silver surface can be polished with a soft jeweller’s cloth. Silver plating that has been completely worn through to the copper below requires re-plating or coil replacement; direct copper without silver increases skin-effect losses. Contact Dan at emtrondv.com for the pi-coil specification. |
C-PLATE / C-LOAD (variable capacitors)
Tune and Load variable air capacitors; 6:1 reduction drives
Category A — unavailable from Dan; wider range needed for 7-band coverage at 1,500 W
|
Category A — Unavailable from Dan. The DX-2 variable capacitors must handle higher RF peak voltages than DX-1 capacitors due to the higher output power. Inspect rotor and stator plates for arc pitting or deformation, particularly at the low-capacitance extreme (tuning the 15–20 m bands). Bearing smoothness is critical; verify the 6:1 reduction drive operates with consistent torque and no roughness. Any replacement must be sourced from a parted-out DX-2 donor unit. |
S-BAND (9-position ceramic switch)
Band switch; 7 active positions (plus 2 spare for future expansion)
Category A — unavailable; silver-plated ceramic wafers
|
Category A — Unavailable from Dan. Despite the 9-position switch, only 7 bands are covered by the DX-2 RF deck. Inspect all wafers for arc damage and carbon tracking, particularly on the 40m and 80m positions where the highest circulating tank currents occur at 1,500 W. Clean with DeoxIT D5 followed by isopropyl alcohol. Contact tracking between adjacent switch wafer positions is a service-ending failure mode on any used Emtron amplifier. |
RF MODULE — A106 (7×) & MOV (275 V)
Anode clamping diodes (7 vs 4 in DX-1D) and screen MOV protection
Seven A106 diodes in clamping arrangement at 140 V; 275 V MOV in screen circuit; from RF module schematic
|
The DX-2 RF module schematic shows seven A106 clamping diodes (vs four in the DX-1D RF module), providing greater transient protection for the more powerful GU84B plate circuit. Additionally, a 275 V MOV in the screen circuit provides suppression of screen voltage transients during tube arc events. Inspect all A106 devices for thermal discolouration after any arc event. An A106 failed short-circuit drags the anode supply toward the clamp level; an A106 failed open leaves the protected circuit unprotected. The 275 V MOV is rated to absorb repeated screen transients; a darkened or cracked MOV body indicates it has absorbed significant energy and should be replaced with a matching device. |
C-PLATE (4× 1,000 pF/6 kV)
Plate bypass capacitors at tube anode
1,000 pF / 6,000 V ceramic; four in RF module schematic; same values as DX-1D but under higher power stress
|
The DX-2 plate bypass capacitors are the same 1,000 pF/6 kV ceramic types as in the DX-1D, but they are under higher stress at 1,500 W output and 2,500 V plate voltage. Replace as a set of four after any plate circuit arc event. Use disc ceramics of minimum 6 kV working voltage only. The DX-2 also shows 2.2 nF and 22 nF capacitors in the RF module circuit for additional filtering; verify these are intact during any RF deck service. |
L-PLATE CHOKE
Plate RF choke; HV feed to tube anode
1" OD, 6" long (Dan stocks); rated for HV plate feed at 2,500 V and 1,500 W plate current
|
Category C — Available from Dan at emtrondv.com. The plate choke specification (1" OD, 6" long) is shared with the DX-1D series; Dan’s stocked choke should also be suitable for the DX-2. However, the DX-2 carries higher plate current than the DX-1D (due to 1,500 W vs 750 W output); verify the replacement choke wire gauge is adequate for the rated plate current at 2,500 V operation. A failed plate choke (cracked former, short circuit) allows RF to appear on the HV supply, stressing the HV filter capacitor bank. |
5. High Voltage Power Supply — 2,500 V Architecture
5.1 Power Supply Architecture
The DX-2 HV power supply follows the same architecture as the DX-1D — transformer, full-wave bridge rectifier, and series-string filter capacitor bank — but the larger GU84B tube and higher plate voltage require a more capable transformer and a larger HV filter bank. The DX-2 manual describes the transformer as “a high performance type, designed to reduce the size and weight” while being built “with a generous reserve of power, handling easily the DX-2 requirements in continuous operation.”
The plate voltage metering divider uses the same 1 Ω plate current sense resistor architecture as the DX-1D: 1 V at TP2 = 1 A plate current. The IPTRIP protection (POT6) and associated adjustment procedure are identical to the DX-1D guide. The screen voltage for the GU84B is significantly higher than for the GU74B; the AMPC board’s TIPL760A screen regulator must sustain the higher screen voltage demanded by the GU84B’s rated G2 operating point.
Component & Description |
Replacement / Notes |
|---|---|
C-HV (filter bank)
HV filter electrolytic capacitor bank
Series string; rated for 2,500 V DC total; individual cap ratings per unit
|
Inspect for bulging, leakage, and thermal stress marks. Verify equal voltage distribution across each series capacitor with a 4,000 V-rated DMM during powered testing. Replace the complete bank as a matched set of same manufacturer, value, and voltage rating; use modern 105°C long-life electrolytic types. Voltage-balancing resistors across each capacitor must be verified intact; a failed bleeder resistor causes progressive voltage imbalance and accelerated capacitor failure. At 2,500 V, an unbalanced series string will apply excess voltage to the weakest capacitor, causing premature breakdown. |
BR-HV (bridge rectifier)
Full-wave bridge rectifier diodes
High-PIV types; matched set; higher current rating needed for DX-2 vs DX-1D
|
Replace as a complete matched set with high-PIV silicon rectifiers (minimum 5 kV per individual diode, or series-stacked with voltage-sharing resistors). The DX-2 transformer secondary peak voltage at 2,500 V nominal plate voltage is approximately 2,800–3,000 V peak; the rectifier diodes must withstand the full reverse peak voltage plus transient spikes. Verify from the DX-2 schematic the exact diode arrangement and replace with equivalents of matching voltage and current ratings. |
R-SENSE (1 Ω plate current)
Plate current sensing resistor at TP2
1 Ω precision wirewound; 1 V = 1 A; must be rated for DX-2 plate current
|
The DX-2 plate current is higher than the DX-1D at maximum rated output (1,500 W vs 750 W). A plate current of approximately 0.6 A at 2,500 V for 1,500 W output (assuming ~60% efficiency) means the sense resistor dissipates approximately 0.36 W during normal operation. Use a wirewound precision resistor of minimum 2 W rating. The IPTRIP threshold must be calibrated after any 1 Ω resistor replacement to ensure the overcurrent protection is set correctly for the DX-2’s higher plate current range. |
6. AMPC Control Board — DX-2-Specific Features & Adjustments
6.1 Screen Voltage Adjustment (POT2) — DX-2-Specific
The DX-2 AMPC control board includes a SCREEN VOLTAGE adjustment (POT2, marked SCREEN) that is not documented as a required adjustment in the DX-1D service procedures. This adjustment sets the regulated G2 screen voltage to the GU84B’s correct operating point. The GU84B datasheet specifies a maximum G2 voltage of 400 V; the DX-2 screen supply is set to the Emtron-specified operating voltage which falls within this maximum.
The screen voltage is measurable at pin EG2 (blue wire) on the AMPC board when the amplifier is in READY/OPR state. After any tube replacement or control board replacement, POT2 must be adjusted to the correct GU84B screen voltage. The DX-2 manual’s service section (Section 15.1.1.5) provides the full adjustment procedure using the EG2 test point.
Component / Adjustment |
DX-2 Notes |
|---|---|
C7 (22 μF tantalum)
Timer capacitor — #1 failure
Same as DX-1A/DX-1D/DX-1SP: READY LED never activates if failed
|
Same diagnosis and replacement as all previous DX guides. Locate T110 pins (yellow wire, top front corner of AMPC board). If 12 V remains indefinitely at T110 after 3 minutes, C7 has failed. Remove C7; if READY activates, replace with 22 μF / 25 V tantalum. Applies identically to the DX-2. |
U5 (LMC555)
Timer IC — secondary failure
Same as DX-1 models; DIP-8 CMOS 555
|
Same diagnosis and replacement as all previous DX guides. Replace with LMC555 (CMOS). Standard DIP-8; universally available. |
Q5 (TIPL760A)
Screen voltage regulator
Higher screen voltage than DX-1D; GU84B G2 rated to 400 V max
|
The DX-2 screen supply voltage is higher than in DX-1D models (GU84B vs GU74B G2 requirements). Verify the TIPL760A is producing correct screen voltage at pin EG2 in READY/OPR. A failed TIPL760A may produce incorrect screen voltage — either below the GU84B’s required level (no output power) or above the 400 V maximum (tube damage). After any TIPL760A replacement, use POT2 to set the screen voltage to the Emtron specification before operating the amplifier. |
POT3 / BIAS
Idle current — required after tube replacement
DX-2 idle current target: 370–380 mA (370–380 mV at 1 Ω sense); clockwise reduces current (vertical board)
|
The DX-2 bias current target is 370–380 mA (measured as 370–380 mV across the 1 Ω sense resistor) for the vertically mounted board — higher than the DX-1D’s 290–310 mA target, reflecting the GU84B’s larger cathode area and higher Class AB1 operating current. Adjust with EBS jumper removed (EBS OFF); restore EBS ON after adjustment. Clockwise rotation reduces plate current on the vertical DX-2 board — same direction as DX-1D. |
POT2 / SCREEN
Screen voltage adjustment — DX-2 specific
Adjusts TIPL760A regulated screen output; measured at EG2 (blue wire); required after tube or control board replacement
|
Required after tube or control board replacement. Measure screen voltage at EG2 (blue wire) with amplifier in READY/OPR. Set to the Emtron-specified operating voltage for the GU84B (consult the DX-2 service section 15.1.1.5 or Dan at emtrondv.com for the target voltage). Do not exceed 400 V (GU84B max G2 rating). An over-voltaged G2 circuit causes immediate tube damage. Factory pre-adjustment is normally stable for many years; only touch POT2 when tube replacement requires recalibration. |
POT6 / IPTRIP
Plate current trip threshold
Same TP2 procedure as DX-1 series; 1 V = 1 A; clockwise increases trip threshold (vertical board)
|
Same adjustment procedure as DX-1 models (inject current into TP2; set trip between 1.0–1.5 A for vertical-board DX-2). The DX-2 operates at higher plate current than DX-1D (higher power output); the IPTRIP threshold should reflect this. Clockwise rotation on the vertically-mounted DX-2 board increases the trip threshold (same direction as DX-1, DX-2SP — confirmed by the DX-3 manual’s adjustment notes: “Rotate clockwise for DX-1, DX-2 and anti-clockwise for DX-2SP and DX-3.”) |
POT1 / IG2LIMIT
Screen current limit (factory-adjusted)
Do not adjust; factory set for GU84B; higher G2 current than DX-1D GU74B
|
Factory-adjusted and should not be changed unless replacing the control board. The GU84B G2 dissipation rating is 30 W (vs GU74B’s lower G2 rating); the screen current limit should be set accordingly. The DX-2 Display Board shows both Ig2+ (positive screen current, normal operation) and Ig2− (negative screen current, occurs during overdrive or certain operating conditions) — unique to the DX-2 and higher models in the range. |
7. Display Board — Ig2+/Ig2− Screen Current Metering
The DX-2 Display Board uses the same LM3914 bargraph IC architecture as the DX-1D, but adds two additional metering channels not present in the DX-1D display: Ig2+ (positive screen current) and Ig2− (negative screen current). These channels are driven from the X3-8 and X3-9 connector pins (confirmed from the DX-2 Display Board schematic). The ability to see negative screen current is directly relevant to the GU84B’s operating characteristics: at high output power, the GU84B can exhibit negative screen current (the screen grid captures some of the electron flow back toward the cathode), which is a normal operating condition for high-power tetrodes but must be monitored to ensure it remains within safe limits.4
Display Board service follows the same procedure as documented in the DX-1D guide: LM3914 IC replacement for failed bargraph channels (still in production from TI/ON Semi), standard bargraph LED module replacement, and Display Board calibration from the DX-2 manual Appendix 3. Calibration of the Ig2+ and Ig2− channels requires a calibrated milliammeter and the DX-2 adjustment procedure; these adjustments should be performed when the tube is replaced.
8. Soft-Start Module — 5-Second Ramp & Safety Capacitors
The DX-2 soft-start module uses the same TDA1085C gate controller and TRIAC architecture as the DX-1D, but with a longer 5-second ramp (vs the DX-1D’s 3 seconds) reflecting the larger transformer and higher filter capacitance of the DX-2 power supply. The manual notes: “The soft start system will take about 5 seconds to fully turn the power on.” The SWR LED briefly lights during this ramp-up as the supply reaches operating voltage.
The DX-2 soft-start schematic (from the DX-2 manual Appendix, referenced in the FCC filing) shows a more elaborate soft-start circuit than the DX-1B version, with additional filtering components (470 kΩ bleeder resistors, 220 μF/25 V electrolytics, 47 nF and 3.3 μF capacitors in the gate drive circuit) to provide a smoother phase ramp over the longer 5-second period. The safety capacitors (Class X2 and Y2) are the same specification as all DX-series amplifiers.
Component & Description |
Requirements |
|---|---|
C-Y2 (4.7 nF/250 VAC)
Line/neutral to chassis (Y-type) safety capacitors
4.7 nF / 250 VAC; Class Y2 certified; fail-open design; lethal if replaced with standard ceramics
|
Class Y2 certification mandatory. A standard ceramic disc capacitor in a line-to-chassis position that fails short-circuit places mains voltage on the amplifier chassis. Replace only with IEC Class Y2 certified components. Confirmed from the DX-2 soft-start schematic showing 4.7 nF/250 VAC/Y2 capacitors (same values as DX-1B/DX-1D). |
C-X2 (470 nF/250 VAC and 220 nF/250 VAC)
Line-to-line (X-type) safety capacitors
470 nF and 220 nF / 250 VAC; Class X2 certified; across AC mains; DX-2 has larger X2 bank than DX-1D
|
Class X2 certification mandatory. The DX-2 soft-start schematic (FCC ID QYNDX-2) shows 470 nF/250 VAC/X2 and 220 nF/250 VAC/X2 types confirmed. Replace with Wima MKX2 or Vishay MKP-X2 series. A failed X2 capacitor blows the mains fuse but does not create a chassis-shock hazard. |
TDA1085C (soft-start controller)
TRIAC gate controller; 5-second ramp
Same as DX-1D; Vcc pin 9 = ~15.6 V; low Vcc causes reduced plate voltage
|
Same diagnosis and replacement procedure as DX-1D. Measure Vcc at TDA1085C pin 9 during operation. Low Vcc causes incomplete TRIAC conduction; plate voltage reads approximately 1,800 V instead of 2,500 V. Replace with TDA1085C (NOS, European distributors) or equivalent phase-control IC. |
9. Safety: Interlock, HV Discharge & Mains
The DX-2 plate supply at 2,500 V DC can cause instantaneous cardiac arrest. The HV filter capacitor bank stores sufficient energy for a fatal discharge. The safe discharge procedure must be followed completely and verified with a meter before every internal access session. The two-sensor temperature monitoring and two-speed blower add additional cable routing in the tube area; take care not to disturb these during service in a way that allows any conductor to contact the HV circuit.
9.1 Mains Not Less Than 200 VAC
Unlike the DX-1 series (which supports 100–240 VAC), the DX-2 must be connected to a mains supply of not less than 200 VAC. This is a specific technical limitation documented in the DX-2 manual and should be verified for any DX-2 that is to be operated outside Australia or Europe. Operation below 200 VAC will reduce plate voltage below 2,500 V, decrease output power, and may stress the transformer secondary by requiring higher primary current to maintain power.
9.2 Safe Discharge Procedure
STEP 1 ── STBY switch to STBY; POWER to OFF.
│
STEP 2 ── DISCONNECT ALL REAR-PANEL LEADS.
Mains cord, antenna cables, PTT/key, ALC.
│
STEP 3 ── Wait minimum 5 minutes.
GU84B has larger thermal mass than GU74B;
allow additional cooling time for the tube.
│
STEP 4 ── ANODE DISCHARGE:
Insulated probe with 10kΩ/25W series resistor
clipped to chassis. Apply to GU84B anode contact.
Hold 10 seconds.
│
STEP 5 ── HV MEASUREMENT:
4000V-rated DMM: probe (+) to HV filter cap positive,
probe (-) to chassis. CONFIRM < 50V DC.
│
STEP 6 ── SCREEN SUPPLY CHECK:
Measure EG2 (blue wire, AMPC board) to chassis.
GU84B screen voltage is higher than GU74B models.
Confirm < 50V.
│
STEP 7 ── BIAS SUPPLY CHECK:
Measure negative bias supply to chassis.
Confirm < 10V absolute value.
│
STEP 8 ── TWO-SENSOR AREA PRECAUTION:
After accessing the tube area, verify both
temperature sensors above the tube are repositioned
near-horizontal before next power-up.
HIGH VOLTAGE EXISTS BETWEEN SENSORS AND TUBE ANODE.
│
STEP 9 ── Re-verify HV bank: < 10V.
│
STEP 10 ── Now safe to work internally.
Figure 1. DX-2 safe discharge procedure, including the two-sensor repositioning reminder unique to the DX-2.
9.3 Cover Safety Microswitch
The cover safety microswitch on the DX-2 interrupts the mains supply when the cover is removed. Verify it operates correctly at every service. The DX-2 manual confirms this interlock is present and is described in the same terms as all Emtron DX amplifiers: defeating it for live adjustments is extremely dangerous.
10. Cabinet & Assembly Hardware
The DX-2 cabinet uses the same 2 mm steel chassis with dark yellow chromate coating, 3 mm anodised aluminium front panel, and baked enamel texture finish as the DX-1 series. The front panel is adapted for 7-band operation and includes the larger dual-speed blower ventilation requirements. Cabinet service follows the same procedures documented in the DX-1D guide, with the additional note that the DX-2 transformer is heavier than the DX-1D transformer; when repositioning the amplifier for bench service, use appropriate lifting technique for the increased weight.
Item & Description |
Notes |
|---|---|
Band switch (9-position)
7 active bands; no 12m or 10m; ceramic; silver-plated; Category A unavailable
|
Category A — Unavailable from Dan. Note: despite the band switch being a 9-position device, only 7 positions are used for the DX-2’s 7-band coverage. Inspect all 7 active positions for arc tracking or carbon deposits. Clean with DeoxIT D5 and isopropyl alcohol. If a field report shows power dropping 45 degrees from the original tune position (as one DX-2 owner reported on a Facebook group), the likely cause is not the band switch but a shift in the HV supply or a tank capacitor issue — verify all voltages and mechanical positions before condemning the switch. |
RF connectors (SO-239)
Input and output; 1,500 W rated service; same as DX-1D standard
|
At 1,500 W, connector integrity is more critical than at 750 W. Any resistive connector joint that would survive DX-1D power levels will fail at DX-2 power levels. Inspect for arc pitting, deformed centre pins, and connector body heat. Replace with silver-plated 4-hole panel-mount SO-239 (Amphenol 83-1R or equivalent). |
Mains fuses
Rear panel; 200–240 VAC; correct current rating critical
|
Verify fuse rating is correct for the installed mains voltage and the DX-2 transformer primary current. Use only certified mains-rated slow-blow fuses. A fast-blow fuse will trip on the transformer inrush even with the soft-start circuit active if the fuse is under-rated for the instantaneous peak current. |
Mains power cable
Three-core; 200–240 VAC only; protective earth essential; higher current draw than DX-1D
|
At 1,500 W output and approximately 60% efficiency, the DX-2 draws approximately 2,500 W from the mains. At 230 VAC, this is approximately 11 A continuous. Use a cable rated for 15 A minimum and install a dedicated circuit if possible. Do not use an extension cord; voltage drop at high current reduces plate voltage below 2,500 V, reducing output power and potentially affecting tube operating parameters. The protective earth conductor must be intact and properly connected at both ends. |
Earth terminal (wing-nut)
Rear panel; first connection before mains; mandatory for all DX models
|
Connect the protective earth terminal to station earth before any other rear-panel connections. Verify earth continuity below 0.5 Ω at every service. The DX-2 manual specifies the same wing-nut earth terminal connection sequence as the DX-1D. |
11. Factory Initial Capacitor Settings Reference (7 Bands)
The DX-2 manual provides a factory-inscribed table of initial Plate and Load capacitor settings on page 2, unique to each serial number (measured during factory test and recorded by the technician). The bands covered and their approximate typical settings into a 50 Ω dummy load are noted below for reference; the factory-inscribed values on the specific unit’s title page are the authoritative reference. Note the absence of 12m and 10m from the DX-2 coverage.
Band / Freq. |
Coil Used |
Plate (typical) |
Load (typical) |
Notes |
|---|---|---|---|---|
| 15m / 21.200 MHz | Pi (copper tube) | Low | Mid | Highest covered band; highest required frequency |
| 17m / 18.100 MHz | Pi (copper tube) | Low-mid | Mid | WARC band; included in DX-2 coverage |
| 20m / 14.200 MHz | Pi (copper tube) | Mid | Mid-high | Primary DX band |
| 40m / 7.070 MHz | Pi + L (toroid) | Mid-high | High | L-coil toroid in circuit; significant capacitance required |
| 80m / 3.600 MHz | Pi + L (toroid) | High | High | L-coil toroid; near maximum capacitance range |
| 160m / 1.800 MHz | Pi + L (toroid) | Max | Max | Lowest band; full capacitance range required |
| 30m / 10.125 MHz | Pi (copper tube) | Mid | Mid | WARC band; if supported (consult factory settings card) |
| 12m / 24.900 MHz | Not covered by DX-2 — band absent from DX-2 RF deck design | |||
| 10m / 28.500 MHz | Not covered by DX-2 — band absent from DX-2 RF deck design | |||
Use only the factory-inscribed values from the serial-number-specific DX-2 title page as the primary reference. The above table provides directional guidance only.
12. Parts Sources & Reference Documents
- emtrondv.com — Dan (former Emtron technician) — emtrondv.com — Version 7 control board (limited; compatible); plate choke 1" OD / 6" long (stocked); free technical advice; refurbished DX amplifiers (pickup Sydney).
- Emtron DX-2 Operating Manual — manualslib.com — Full service manual including all schematics (HV supply, control board, soft-start, QSK, RF module, display board), adjustment procedures, and internal component layout.
- Emtron DX-2 FCC Filing (FCC ID QYNDX-2) — fccid.io/QYNDX-2 — US FCC filing confirming DX-2 compliance and providing supplementary schematic detail.
- GU84B Datasheet (OK1RR) — ok1rr.com/tubes/gu84b.pdf — Key parameters: 2,500 W plate dissipation; 27 V / 3.7 A heater; 2,200 V max CW anode voltage; 400 V max G2; 3-minute warm-up; 96 m³/h cooling.
- GU84B Tube Sources (NOS) — DL3JJ / QRO-Shop (qro-shop.com); RF Parts Co. (rfparts.com); Soviet-Tubes.com. Mandatory NOS gettering (12–16 hours heater-only) before plate voltage. Verify heater voltage (27 V) at tube socket before installation.
- Mouser / DigiKey — mouser.com / digikey.com — Class Y2 and X2 safety capacitors; LMC555; TIPL760A equivalents; 7805; BC547; 275 V MOV devices; 1,000 pF/6 kV disc ceramics; LM3914 bar-graph ICs.
- Jennings Technology (QSK vacuum relay) — jenningsrelays.com; RF Parts Co. — Jennings TJ1A-26S as used in all Emtron QSK modules.
- SP5BTB DX-1B Field Service Log — qsl.net/sp5btb/dx1b.html — C7/U5 diagnosis; TDA1085C repair; IPTRIP adjustment. All procedures apply to DX-2.
References & Footnotes
- Emtron (Division of Emona Electronics Pty Ltd). DX-2 Operating Manual. manualslib.com. “The Emtron DX-2 Linear Amplifier is a 1500 watt carrier output power, for the 160m through 15m amateur bands (7 bands) … It utilises a single high performance tetrode, type GU84B (4CX2500), a ceramic metal tube with a plate dissipation of 2500W.” ↩
- GU84B Datasheet, OK1RR. Heater parameters: nominal 27.0 V; limits 25.6–28.4 V; current 3.7 A nominal (3.4–4.0 A limits). Maximum CW anode voltage 2,200 V; G2 max 400 V; plate dissipation 2,500 W; design life 1,500 hours. ok1rr.com/tubes/gu84b.pdf. ↩
- Emtron DX-2 Operating Manual, Section 8: DX-2 Description, RF Section. “At the front of the amplifier are two variable capacitors, for plate and load tuning and a band switch. Next to the switch is the ‘Pi’ coil. The ‘L’ coil is wound on a ferrite torroid. The GU84B tube is positioned on a separate RF sub-chassis … A 9-way heavy duty connector is used for inter-connections. The plate is connected to the RF network and to the choke supplying the 2500VDC voltage to the plate of the GU84B tube.” usermanual.wiki. ↩
- Emtron DX-2 Operating Manual, Circuit Diagram — Display Board. Connector X3-8 and X3-9 labelled as “Ig2−” and “Ig2+” on the display board schematic, confirming dual-polarity screen current metering. Also confirmed in the DX-2 manual Section 15.1 General Service: “All Emtron amplifiers are built in a modular form. Most modules are common for the entire DX-n range.” manualslib.com. ↩