Emtron DX-2SP Linear Amplifier:
Restoration & Service Guide
GU84B • 2,000 W Carrier / 2,500 W PEP • 4 kVA Transformer • Heavy-Duty H.V./H.C. Band Switch • Horizontal AMPC Board • Dual-Polarity Screen Supply • BTA40-600B TRIAC Soft-Start • 9 Bands 160m–10m incl. WARC • Later Production: FU-728F Tetrode Option
The DX-2SP operates at a higher plate voltage than the standard DX-2’s 2,500 V DC, consistent with its 2,000 W carrier output from the same GU84B tube. Emtron’s own product description emphasises a “very special high voltage, high current band switch” — the “high voltage” descriptor refers to the elevated plate supply, not merely to normal HF amplifier voltages. The DX-3SP manual notes that the 4 kVA transformer installation requires two people. This amplifier is more dangerous than the DX-2 and DX-2A due to the higher plate supply voltage.
- Disconnect all rear-panel leads before removing the cover — mains, RF, PTT, ALC, accessories.
- Wait minimum 10 minutes after power-off; the larger HV filter bank takes longer to discharge than the DX-2.
- Discharge GU84B anode to chassis through a 10 kΩ/25 W insulated probe before touching any internal component.
- Measure with a 4,000 V-rated DMM; confirm <50 V DC at all supply rails before any internal access.
- The 4 kVA transformer requires two people for installation or removal; back injury risk if attempted solo.
- Cover safety microswitch is the primary interlock; never defeat it.
1. The DX-2SP in Context — Five Differentiating Features
Emtron’s marketing for the DX-2SP, distributed via Radioworld UK and the eHam.net product page, identifies the amplifier as follows: “Besides the tube and a very special high voltage, high current band switch, as well as a 4 KVA mains transformer, the DX-2SP is identical to our DX-2.” 1 When the service literature is consulted alongside the marketing, five distinct differentiating features emerge:
- 4 kVA mains transformer. The DX-2’s standard transformer is replaced by a 4 kVA unit capable of sustaining 2,000 W continuous output. This substantially increases the weight of the amplifier. The DX-3 manual states that the transformer installation “requires two people.” The same applies to the DX-2SP.
- Heavy-duty “high voltage, high current” band switch. The 9-position ceramic band switch is a higher-specification part rated for the elevated RF tank voltages and higher circulating currents associated with 2,000 W operation.
- Elevated plate supply voltage. Producing 2,000 W carrier from the same GU84B tube as the 1,500 W DX-2 requires a higher plate supply. Emtron’s own wording refers to the “high voltage” band switch in the context of the DX-2SP specifically, directly indicating a higher-than-DX-2 plate supply.
- Horizontally-mounted AMPC control board. The Emtron DX-3 operating manual (April 2005) confirms: “Rotate clockwise for DX-1, DX-2 and anti-clockwise for DX-2SP and DX-3, which have horizontally installed boards.” 2 This is the most critical service-differentiation point in the entire DX-2SP guide; getting this wrong will reduce protection sensitivity when the operator intends to increase it.
- Dual-polarity regulated screen supply. The DX-2SP introduces a fully-regulated screen grid supply covering both positive and negative screen current conditions — a protection design unique to the SP family. The Emtron marketing states: “Fully voltage regulated for +ve and −ve screen currents, combined with very effective current limiting, not only totally protects the GU-84B tube, but also due to its wide dynamic range, keeps the tube static operation parameters absolutely stable.”3
The Emtron DX-2 operating manual (2002) states: “Rotate clockwise for DX-1, DX-2, and DX-2SP.” The Emtron DX-3 operating manual (April 2005) states: “Rotate clockwise for DX-1, DX-2 and anti-clockwise for DX-2SP and DX-3, which have horizontally installed boards.” These two official documents directly contradict each other for the DX-2SP. The DX-3 manual (2005) is the more recent document and uniquely identifies the horizontal board as the reason for the reversed direction. It is the correct reference. The DX-2 manual’s 2002 instruction for DX-2SP appears to have been in error, listing DX-2SP alongside vertical-board models before the horizontal board distinction was documented. For the DX-2SP, turn counter-clockwise to increase protection sensitivity; clockwise to decrease it.
2. DX-2SP Technical Specifications
| Output Power | 2,000 W carrier / 2,500 W PEP; all 9 bands, all modes |
| Frequency Coverage | All 9 amateur HF bands: 160, 80, 40, 30, 20, 17, 15, 12, 10 m (all WARC bands) |
| Final Tube (early production) | Svetlana GU84B (= 4CX2500A); 2,500 W plate dissipation; 27 V / 3.7 A heater; Class AB1 |
| Final Tube (later production) | FU-728F (Chinese mil-grade improved 4CX1500B); 1,200 W plate dissipation; 9 V / 8.5–9 A heater; 4CX1500B socket and base-compatible |
| 4CX1500B Compatibility | Yes; change filament tap 9 V (FU-728F) → 6 V (Eimac 4CX1500B); tap included on transformer |
| Band Switch | 9-position ceramic; all positions active; heavy-duty high-voltage / high-current type (unique to DX-2SP) |
| Plate Supply Voltage | Higher than DX-2’s 2,500 V DC; consistent with 2,000 W carrier from GU84B; exact value set by 4 kVA transformer secondary |
| Screen Supply | Dual-polarity regulated; protects +ve and −ve screen current; wide dynamic range (SP-family exclusive feature) |
| Soft-Start TRIAC | BTA40-600B; 3-second linear ramp; 20 A continuous rating |
| HV Filter Bank | 8× 470 µF / 500 V electrolytic; 58 µF total; 4,000 V DC rating (per DX-1SP marketing; shared SP-family design) |
| Mains Fuses | Two 30 A normal-acting (per DX-3SP block diagram including DX-2SP) |
| Mains Input | 200–240 VAC; up to 16 A at 240 VAC; minimum 200 VAC |
| Transformer | 4 kVA; primary taps for 200/220/230/240 VAC; two-person installation |
| AMPC Board Orientation | Horizontal (unlike DX-1/DX-2/DX-2A vertical boards); counter-clockwise = increased protection sensitivity |
| T/R Switching | Standard antenna relay; optional Jennings TJ1A-26S QSK (FCC-listed models); factory-fitted QSK standard in some export configurations |
| Blower | Two-speed commercial turbine; temperature-sensor controlled (same architecture as DX-2) |
| Temperature Sensors | Two sensors above tube; near-horizontal orientation mandatory |
| Display Board | LM3914 bargraph ICs; Ip, Vp, forward/reflected power, Ig2+ and Ig2− |
| RF Sensor | Forward power calibration reference: 2,000 W for DX-2SP (per DX-2 and DX-3 manuals, VR1 / RF F potentiometer) |
| QSK Module | Optional (US$100 factory-installed at purchase); Jennings TJ1A-26S vacuum relay; hot-switching prevention by relay-first sequencing |
| Duty Cycle | CW: 4 min TX / 1 min RX; AM: 3 min TX / 1 min RX; SSB: continuous; RTTY/FM: continuous at full rated power |
| Cabinet | 2 mm steel chassis; dark yellow chromate coating; 3 mm anodised aluminium front panel; baked enamel texture finish |
| FCC Status | FCC-approved (US market); early production GU84B model |
| Warranty | Four years; full parts and labour except tube (tube: limited 4-year warranty) |
| Manufacturer | Emtron, Division of Emona Electronics Pty Ltd; 92–94 Wentworth Avenue, Sydney NSW 2010, Australia |
3. DX-2SP vs DX-2 / DX-2A — Side-by-Side Comparison
Feature |
DX-2 (7-band) |
DX-2A (9-band) |
DX-2SP (Special Performance) |
|---|---|---|---|
| Output Power | 1,500 W carrier | 1,500 W carrier | 2,000 W carrier / 2,500 W PEP |
| Tube | GU84B | GU84B | GU84B (early) or FU-728F (later) |
| Plate voltage | 2,500 V DC | 2,500 V DC | Higher than 2,500 V (elevated for 2,000 W output) |
| Transformer | Standard DX-2 type | Same as DX-2 | 4 kVA; substantially heavier; two-person install |
| Band switch | Standard 9-position (7 active) | Standard 9-position (all 9 active) | Heavy-duty H.V./H.C. 9-position; all 9 active |
| Band coverage | 160m–15m only (7 bands) | All 9 bands incl. 12m + 10m | All 9 bands incl. 12m + 10m + WARC |
| Screen supply | Single-polarity regulated | Single-polarity regulated | Dual-polarity regulated (+ve and −ve); SP exclusive |
| AMPC board orientation | Vertical | Vertical | Horizontal (critical service difference) |
| IPTRIP / sensitivity pot direction | Clockwise = more sensitive | Clockwise = more sensitive | Counter-clockwise = more sensitive (horizontal board) |
| Soft-start TRIAC | Standard TRIAC | Same as DX-2 | BTA40-600B; 20 A rating; 3-second ramp |
| Mains fuses | 2× 20 A | 2× 20 A | 2× 30 A (per DX-3SP block diagram) |
| Forward power calibration | 1,500 W | 1,500 W | 2,000 W (VR1 / RF F) |
| RF sensor calibration | 1,500 W reference on 20m | 1,500 W reference on 20m | 2,000 W reference on 20m |
| QSK standard? | Optional (+US$100) | Optional | Optional (+US$100); standard on some export versions |
4. Final Tube — GU84B (Early) and FU-728F (Later Production)
4.1 Early Production: GU84B (4CX2500A)
The original DX-2SP was built around the Svetlana GU84B, the same ceramic-metal tetrode used in the DX-2 and DX-2A. The GU84B was described in Emtron’s marketing as “produced for the military” and “physically and electrically exceptionally rugged”; its 2,500 W plate dissipation and rated operation up to 250 MHz make it a conservative choice at HF frequencies even at 2,000 W output levels.4 At the higher plate voltage used in the DX-2SP, the GU84B operates closer to its maximum plate dissipation than in the DX-2; thermal management and the two-speed blower are correspondingly more important. NOS GU84B tubes require the standard Emtron gettering procedure (12–16 hours heater-only operation before applying plate voltage). Current-production tubes from verified suppliers do not require gettering.
4.2 Later Production: FU-728F (Improved Chinese 4CX1500B)
A later production revision of the DX-2SP, DX-1SP, and DX-3SP substituted the FU-728F for the GU84B. A WorldwideDX forum post by an Emtron distributor confirmed: “The all new range of Emtron Amplifiers are now using the FU-728F tetrode and using the Eimac 4CX1500B base so you can still use the older 4CX1500B in the same amp. You have to change the voltage on the power supply but the tap is included also.” 5 The FU-728F is a Chinese military-grade tetrode with a 1,200 W plate dissipation rating (compared to the GU84B’s 2,500 W), a 9 V / 8.5–9 A heater, and the standard Eimac 4CX1500B octal socket. At the DX-2SP’s higher power levels, the FU-728F is used significantly above its conservative 1,200 W plate dissipation rating but within the tube’s actual operating envelope; DX-3SP marketing confirms the FU-728F “quite comfortably delivers 2000 W CW” and notes it is “in current factory production” ensuring supply availability.
The FU-728F and 4CX1500B share the same octal base; the GU84B uses a different (larger) socket. A DX-2SP with an FU-728F installed will visually appear different from a GU84B unit — the tube is smaller and the blower duct geometry at the base may differ. To substitute a 4CX1500B Eimac for the FU-728F, change the filament transformer tap from 9 V to 6 V using the included tap. To substitute the GU84B in a later FU-728F DX-2SP, the reverse tap change (6 V → 9 V for GU84B’s 27 V heater would not apply directly; the GU84B heater is 27 V AC, requiring a different transformer winding). Contact Dan at emtrondv.com before attempting cross-generation tube substitutions.
5. The 4 kVA Mains Transformer — Installation & Service
The 4 kVA transformer is the single most physically significant difference between the DX-2SP and the DX-2 / DX-2A. It occupies the same chassis position as the standard DX-2 transformer but weighs considerably more; the DX-3 manual (for a comparable transformer installation) explicitly warns: “Two people are needed to install the transformer. The best is to put the DX-3 on a flat, smooth surface such as a bench or table top, covered by a small carpet or a folded blanket, so that it can be moved by sliding.” The DX-2SP transformer, rated at 4 kVA and providing the higher HV secondary for 2,000 W operation, should be treated identically.
The primary side of the 4 kVA transformer has four taps for 200, 220, 230, and 240 VAC. Correct tap selection is mandatory; under-tapping (connecting to 200 V when the supply is 240 V) will raise the HV secondary proportionally and elevate the already-higher-than-DX-2 plate supply to potentially dangerous levels. When relocating a DX-2SP to a different country or mains voltage regime, confirm the correct primary tap position before any power-on, following the transformer connection diagram on page 2 of the DX-2 operating manual (procedure applies to DX-2SP). This change must be performed by a qualified technician with all power disconnected.
6. Heavy-Duty High-Voltage / High-Current Band Switch
The DX-2SP’s 9-position ceramic band switch is a higher-specification part than the equivalent component in the DX-2 and DX-2A. Emtron’s own product text describes it as “a very special high voltage, high current band switch” — the emphasis on both voltage and current ratings reflects the demands of 2,000 W operation: higher tank RF voltages (from the elevated plate supply) and higher circulating tank currents (from higher RF output power) than the DX-2’s 1,500 W design point. At 28.5 MHz (10m), the combination of high RF voltage and tight capacitor settings places maximum stress on the switch contacts and ceramic wafer insulation.
Component |
Service Notes |
|---|---|
S-BAND (9-pos; H.V./H.C.)
Heavy-duty ceramic 9-position band switch
Category A — unavailable from Dan; higher-spec than DX-2 standard switch; all 9 positions active
|
Category A — Unavailable.
The DX-2SP band switch is the highest-specification single-tube switch in the Emtron range.
Inspect all wafers for arc tracks using a magnifier and strong LED torch; the elevated
plate voltage means arcing leaves deeper carbon deposits than in the DX-2. Clean
each wafer face with DeoxIT D5 followed by 99% isopropyl alcohol on a lint-free swab;
allow full evaporation before applying power. Inspect the switch stator plates and rotor
contact wipers for mechanical wear; at 2,000 W the contact pressure is critical.
A band switch that arcs consistently on 10m or 12m (highest RF voltage positions) may
have cracked ceramic insulation that cannot be repaired; a donor DX-2SP must be sourced
for replacement. Never apply contact lubricant to the RF switching contacts; lubrication
attracts atmospheric contamination and reduces the contact self-cleaning action. |
C-PLATE / C-LOAD (6:1 reduction drives)
Tune and Load variable air capacitors
Category A — unavailable; must handle elevated plate voltage; 6:1 reduction drives critical for 2,000 W tuning precision
|
Category A — Unavailable.
The variable capacitors must withstand the elevated RF peak voltage at the DX-2SP’s
higher plate supply. Inspect the minimum-capacitance end of the plate capacitor for
arc damage across the rotor-stator air gap; this is the highest-stress point at 10m
and 12m. Verify the 6:1 reduction drive meshes produce smooth, non-binding rotation
at both extremes of travel. A bent or misaligned capacitor plate causing intermittent
arcing at full power must be corrected or the capacitor replaced; do not operate the
DX-2SP at 2,000 W with a known arcing variable capacitor. |
L-COIL (ceramic bobbin, 40–160 m)
Low-band pi-coil; ceramic-bobbin wound
Silver-plated; higher power stress than DX-2A at 2,000 W; Category A for sourcing
|
Carries higher circulating tank currents than the DX-2A (2,000 W vs 1,500 W at the same frequencies). Inspect the entire length of the winding for hot spots (discolouration of the silver plating or ceramic former). A crack in the ceramic bobbin under a winding turn is difficult to see but causes inductance instability on the affected bands; symptom is inability to achieve full output on one or more low bands while other bands tune normally. The DX-2SP marketing confirms: “All RF components such as band switch, tank coils, chokes, etc. are of high quality silver plating, ceramic bobbin for lower frequencies is also used.” |
PI-COIL (copper tube, 10–30 m)
High-band pi-coil; large-diameter silver-plated copper tube
Handles highest RF voltage in amplifier at 10m; Category A
|
At 2,000 W into 10m, the RF peak voltage at the plate capacitor can exceed several kilovolts. The silver-plated copper tube at both ends of the pi-coil (the connection points to the band switch and to the Tune capacitor) must be inspected for silver-plating wear, corrosion, and loose mechanical connections. A high-resistance connection at the pi-coil ends at 28.5 MHz causes local heating, RF loss, and degraded output on 10m before causing visible failure. Clean with jeweller’s rouge cloth if tarnished; verify firm mechanical contact at both ends. |
7. High Voltage Power Supply — Elevated Voltage, Larger Filter Bank
The DX-2SP HV power supply provides a higher plate voltage than the DX-2’s 2,500 V DC, sustained by the 4 kVA transformer. The HV filter bank uses eight 470 µF / 500 V electrolytic capacitors in a series-parallel arrangement, providing 58 µF total at a 4,000 V DC working voltage — the same architecture described in the DX-1SP marketing for the SP-family supply, which uses identical components and layout at 1,200 W. In the DX-2SP, this bank is under higher continuous stress due to the combination of higher voltage and higher supply current drawn at 2,000 W output.
Component |
Service Notes |
|---|---|
C-HV (8× 470 µF / 500 V)
HV filter bank electrolytics
Series-parallel array; 58 µF / 4,000 V DC rating; replace as complete bank
|
Replace all eight capacitors as a matched bank whenever one is found faulty; a bank with mixed new and aged capacitors will not share voltage equally in the series string, placing the oldest capacitors at elevated voltage stress. Use 105°C-rated 470 µF / 500 V electrolytics from Mouser, DigiKey, or Nichicon direct. Verify the individual equalising resistors across each capacitor are intact (typically 100 kΩ / 2 W for each section) before installing the replacement bank. At the DX-2SP’s elevated plate voltage, failed equalising resistors allow one capacitor to see the full supply voltage, causing catastrophic failure. |
D-HV (full-bridge rectifier)
HV rectifier diodes; full-wave bridge
PIV must exceed DX-2SP plate voltage by ≥2× safety margin; use ≥6 kV series strings
|
The rectifier diodes must have a total PIV rating comfortably exceeding the DX-2SP’s elevated plate voltage with a ×2 safety margin at minimum. Series diode strings of 1N4007 (or equivalent 1 kV / 1 A) with equalising resistors are the standard Emtron approach. After any transformer-side fault or surge, test rectifier continuity; a single shorted diode in a series string halves the PIV of that leg. Replace individual strings as complete units, not individual diodes. |
R-HV (25 Ω / 50 W bleeder/protection)
HV bleeder and flash-over protection resistor in B+ line
Non-inductive wirewound; limits fault current during tube flash-over; check after any HV fault event
|
The DX-3SP marketing confirms a 25 Ω / 50 W resistor in the HV B+ circuit protects against tube internal flash-over. After any tube flash-over event in the DX-2SP, this resistor is the first component to check; it will show elevated resistance or open circuit if the fault current was sufficient. Replace with identical or higher-wattage non-inductive wirewound type; do not substitute inductive wirewound or carbon resistors. |
MOV (275 V; screen circuit)
275 V Metal Oxide Varistors in screen circuit
Multiple MOV devices per DX-2 RF module schematic; check after arc or screen-current fault
|
The DX-2 RF module schematic shows a 275 V MOV in the screen circuit protection chain alongside the A106 clamping diodes. After any screen current fault, inspect all MOV devices for physical damage (cracking, swelling, or discolouration). A failed MOV passes high leakage current and will destabilise the screen voltage regulation. Replace with exact specification (275 V, same package). Insist on certified Littelfuse or Bourns parts; no-name MOV devices have poor clamping consistency. |
8. Soft-Start Module — BTA40-600B TRIAC & Safety Capacitors
The DX-2SP soft-start module uses a BTA40-600B TRIAC (40 A, 600 V) in a phase-controlled 3-second linear ramp circuit, documented in the DX-3SP operating manual (February 2009), which includes the complete DX-2SP soft-start schematic as a sub-diagram within the DX-3SP block diagram section.6 The 3-second ramp charges the HV filter bank electrolytics slowly and linearly — Emtron’s marketing emphasises this eliminates both transformer inrush and capacitor inrush, meaning “stress in components, failure and ‘transformer bong’ are non-existent.”
Component |
Value & Class |
Position in Circuit |
Replacement Requirement |
|---|---|---|---|
| Y2 safety caps (×2) | 4.7 nF / 250 VAC / Class Y2 | Line-to-chassis (mains side) | Class Y2 certification mandatory; prevents lethal shock via chassis contact if line fails to chassis; standard 50/60 Hz ceramic disc caps must NOT be used. Sourced from Mouser/DigiKey. |
| X2 safety cap (×1) | 470 nF / 250 VAC / Class X2 | Line-to-neutral (across mains) | Class X2 certification mandatory; must withstand mains transients without violent failure; standard MKT film caps are not equivalent. Kemet, Vishay, or Wima X2 types. |
| X2 safety cap (×1) | 220 nF / 275 VAC / Class X2 | Across mains switch/load | Same Class X2 requirement as above; 275 VAC rating is minimum; do not substitute 250 VAC types in this position. Verified from DX-3SP soft-start schematic applicable to DX-2SP. |
| Gate current caps (×2) | 2.2 nF ceramic | TRIAC gate circuit | Standard ceramic; not safety-rated; can be replaced with equivalent 2.2 nF 630 V ceramics. Both must be replaced together to ensure matched gate timing. |
Component |
Service Notes |
|---|---|
BTA40-600B TRIAC
Phase-controlled soft-start TRIAC; 40 A / 600 V
Mounted on chassis for heat-sinking; phase control IC drives gate; 3-second linear ramp
|
The BTA40-600B is the most likely single component to fail in the soft-start module under conditions of repeated power cycling, brownout, or supply transients. Symptom of failure: no soft-start ramp — either immediate full-power-on (TRIAC shorted) or no power-on at all (TRIAC open). The BTA40-600B is a standard STMicroelectronics-family part; verify the TO-220 case mounting to the chassis is clean and tight with thermal compound before installation. A failed TRIAC will show <2 Ω between MT1 and MT2 on resistance measurement if shorted. Insist on STMicroelectronics BTA40-600B or verified equivalent; counterfeit TO-220 devices with BTA40 markings are common from grey-market suppliers. |
TDA1085C (soft-start controller IC)
Phase-control IC; drives TRIAC gate for 3-second ramp
DIP-16; TDA1085C; pin 9 = Vcc = 15.6 V (verify as per DX-1D service data); check before condemning TRIAC
|
The TDA1085C phase-control IC drives the BTA40-600B gate and determines the 3-second ramp profile. Before condemning the TRIAC, verify the TDA1085C is functional: apply a regulated 15–16 V to pin 9 (Vcc) isolated from the mains circuit and observe pin outputs. A failed TDA1085C typically produces either no gate drive (TRIAC never fires) or immediate full-conduction gate drive (bypasses soft-start). Exact same IC used in DX-1 series, DX-2, and DX-3; widely available from Mouser as TDA1085C in DIP-16 package. |
Mains Fuses (2× 30 A fast-acting)
Primary mains protection; two fuses in line
30 A; normal-acting; DX-3SP block diagram confirms 30 A for DX-2SP (larger than DX-2’s 20 A fuses)
|
The DX-2SP uses 30 A fuses, not the DX-2’s 20 A fuses. The DX-3SP operating manual block diagram (which includes the DX-2SP circuit) shows 30 A fuses for both models at this power level. Never install 20 A fuses in a DX-2SP; they will blow under sustained 2,000 W operation. Never over-fuse with anything above 30 A; the fuses are the last protection against a transformer or wiring fault. Standard IEC/Australian 30 A ceramic fuses. |
9. AMPC Control Board — Horizontal Orientation & Reverse Pot Direction
The AMPC control board in the DX-2SP is mounted horizontally rather than vertically as in the DX-1, DX-2, and DX-2A. This single physical difference reverses the effective rotation direction of all sensitivity potentiometers relative to the component orientation seen by the technician. The Emtron DX-3 operating manual confirms definitively: “Rotate clockwise for DX-1, DX-2 and anti-clockwise for DX-2SP and DX-3, which have horizontally installed boards — access on the component side.” 2
Adjusting any AMPC potentiometer on the DX-2SP in the wrong direction will reduce protection sensitivity when the operator believes they are increasing it. An amplifier with insufficient IPTRIP sensitivity can deliver full plate current into a shorted output, damaging the tube and potentially starting a fire. Always verify the direction by observing plate current response immediately when making any AMPC adjustment on the DX-2SP: counter-clockwise rotation should reduce plate current (increase sensitivity / tighten trip); if the current increases with counter-clockwise rotation, you have the wrong model’s adjustment direction and must stop immediately.
Pot / Label |
DX-2SP Notes (horizontal board; counter-clockwise = more sensitive) |
|---|---|
POT3 / BIAS |
GU84B target: 370–380 mA (370–380 mV
across 1 Ω sense resistor). FU-728F target: similar idle current level; verify with
Dan at emtrondv.com. EBS jumper must be removed during bias adjustment; restore
immediately after. Counter-clockwise reduces current (horizontal board orientation).
After any tube replacement, perform bias adjustment before applying full RF drive. |
POT2 / SCREEN |
Screen voltage adjustment for dual-polarity supply. Measure at EG2 (blue wire)
in READY/OPR. The DX-2SP’s dual-polarity screen supply has both positive and negative
regulated rails; the POT2 adjustment sets the operating point. Do not exceed maximum G2
voltage (400 V for GU84B; verify FU-728F datasheet for FU-728F units). Required after
any tube or control board replacement. |
POT6 / IPTRIP |
Protection sensitivity (IPTRIP). Use 140 Ω / 130 Ω resistive
load jig (2.7:1 SWR threshold). Counter-clockwise increases sensitivity (tighter
trip) for horizontal board. Verify on 20m at nominal 2,000 W forward power.
The protection should trip at 140 Ω and not at 130 Ω. |
VR1 / RF F (forward power) |
RF sensor forward power calibration. On 20m at full rated output into 50 Ω
dummy load, set VR1 so the Vp bargraph displays 2,000 W as confirmed
by an external calibrated wattmeter (Bird 43 or equivalent). This is the RF Sensor
Adjustment procedure from the DX-2 and DX-3 manuals, applied to the DX-2SP’s
2,000 W reference level. A VR1 calibrated to 1,500 W (DX-2 level) will show
incorrectly low forward power on the bargraph and may fail to trigger SWR protection at the
correct threshold. |
POT7 / PRE-BIAS |
EBS cutoff bias; adjust with EBS jumper fitted (EBS ON). Same procedure as DX-2.
Counter-clockwise direction for horizontal board. |
POT1 / IG2LIMIT |
Screen current limit; factory-set; do not adjust without factory guidance.
The DX-2SP’s dual-polarity screen supply makes IG2LIMIT more sensitive than
in the DX-2; verify Ig2+ and Ig2− bargraph readings are stable at full power on
all 9 bands. Both Ig2+ and Ig2− channels must track smoothly; erratic Ig2−
readings indicate the negative screen current regulation is unstable. |
10. Dual-Polarity Screen Supply — SP-Family Exclusive Design
The DX-2SP’s screen grid supply is the most technically advanced in the DX-2 family. Emtron’s description of the design is worth quoting precisely: “Yet another unique new design, exclusive to the EMTRON DX-2SP amplifier is its screen grid power supply. Fully voltage regulated for +ve and −ve screen currents, combined with very effective current limiting, not only totally protects the GU-84B tube, but also due to its wide dynamic range, it keeps the tube static operation parameters absolutely stable. The protection against excessive screen current is so good, that we have tested the operation with full screen voltage, while the plate voltage was absent, for extended time, without damage to the tube.” 3
In conventional tetrode amplifier screen supplies, the screen takes positive current during normal RF drive and can draw negative (reversed) current during specific transient conditions such as high SWR events, overdrive, or plate voltage loss. A single-polarity screen supply (as used in the DX-2 and DX-2A) may not handle reversed screen current gracefully; the DX-2SP’s dual-polarity regulation absorbs both current directions with equal stability, preventing screen voltage excursions during fault conditions that could otherwise damage the tube.
Component |
Service Notes |
|---|---|
TIPL760A (screen regulator transistor)
Screen voltage regulator pass transistor; TMOS Power FET type; SP-family screen supply
TIPL760A or equivalent N-channel high-voltage MOSFET; check after any screen current fault
|
The TIPL760A (and its dual-polarity counterpart in the negative rail) is the principal failure point in the SP-family screen supply. Symptoms of failure: incorrect screen voltage at EG2 (too high or too low), erratic Ig2+ or Ig2− bargraph readings, or tube protection trips at low RF drive. After any screen-over-voltage event, test the TIPL760A with a DMM in diode mode (gate-source, gate-drain, source-drain); a shorted TIPL760A will show near-zero resistance across its drain-source. Replacement: TIPL760A (STMicroelectronics); ensure thermal contact to heatsink or chassis mounting point is restored with fresh thermal compound. |
A106 / MOV (screen clamp diodes and MOV)
Screen circuit clamping diodes (140 V clamp level) and 275 V MOV
Per DX-2 RF module schematic; multiple A106 diodes at 140 V clamp; 1N4148 and 275 V MOV also present
|
The A106 diode array in the screen circuit provides fast clamping if the screen voltage exceeds 140 V. After any flashover or screen-fault event, test each A106 in circuit with a DMM (forward voltage drop); a conducting A106 in reverse will show near-zero resistance and clamp the screen permanently below operating voltage. Replace A106 devices as a group; the DX-2 RF module schematic shows their exact quantity and position in the screen path. Confirm 275 V MOV is intact (should show near-open circuit until clamping voltage is reached). |
C7 (tantalum timer capacitor; AMPC board)
Warm-up timer capacitor; controls READY LED delay
Electrolytic (tantalum preferred); located in top-front corner of AMPC board; primary aging failure
|
Identical failure mode to all Emtron DX amplifiers. Symptom: READY LED never illuminates (stuck waiting); READY LED illuminates immediately on power-on (no warm-up delay). Dan’s procedure: verify pin T110 (yellow wire) voltage goes to <1 V within 3 minutes on power-up; if it stays at 12 V, C7 is confirmed faulty. Remove C7; amplifier can be operated without C7 for testing (observe warm-up time manually). Replace with tantalum type of same value. On the DX-2SP’s horizontal AMPC board, C7 is found at the component-side corner closest to the front panel. |
U5 (LMC555 timer IC)
Warm-up timer; works with C7 to produce READY delay
LMC555 CMOS; secondary fault if C7 replacement does not resolve timer issue
|
If replacing C7 does not restore correct READY delay, the LMC555 (U5) is the next suspect. Same replacement procedure as DX-1/DX-2 series. The LMC555 CMOS type must be used, not the bipolar NE555; the LMC555’s lower supply current and cleaner output thresholds are required for correct timer operation at the AMPC board’s supply voltage. |
M4-12H (PCB relay; ×2 on AMPC board)
PCB-mount signal relays for EBS and OPR/STBY switching
12 V coil; limited stock from Dan; replace in pairs
|
Same relay and failure mode as DX-2. Symptoms: EBS activates immediately (dirty contacts passing RF back), or STBY/OPR switching intermittent. Clean contacts with DeoxIT R5 relay contact cleaner as first step. If contact resistance remains above 1 Ω, replace. Dan has limited stock. Replace as a matched pair if either is faulty. |
EBS JUMPER (solder-side; AMPC board)
Electronic Bias Switch enable jumper; solder-side of AMPC board
Default: EBS ON (jumper fitted); frequently lost during service
|
The EBS jumper is the most commonly lost component during DX-2SP service. On the horizontal AMPC board, the solder side of the board faces upward (component side faces the chassis base), making the jumper position immediately visible when the top cover is removed. Default is EBS ON. Symptom of missing jumper: abnormally high idle plate current immediately on entering OPR; EBS threshold adjustment has no effect. Restore jumper before any power testing. |
11. Safety Systems — Interlocks, Discharge, & Safe Working Practice
11.1 Cover Safety Microswitch
The DX-2SP cover safety microswitch interrupts the mains supply when the top cover is removed. At the DX-2SP’s elevated plate voltage, this interlock is more critical than in the DX-2. The Emtron DX-3 manual warns (and the text applies equally to the DX-2SP): “Most of the following adjustments require the amplifier to be open and powered up. This also implies defeating the mains interlock safety switch, which is extremely dangerous since high voltage / high power DC and AC and RF voltages are exposed.” Defeat the safety microswitch only for the specific adjustment requiring it; restore it immediately upon completion. A defective microswitch must be replaced with an identical type before returning the amplifier to service.
11.2 RF Module Safety — Temperature Sensor Position
The two temperature sensors above the GU84B (or FU-728F) tube must remain in a near-horizontal position after any RF deck service. The Emtron DX-2 manual warns: “The sensors must stay in a position close to horizontal. Make sure you are not pushing them down, too close to the tube, as high voltage exists between them.” At the DX-2SP’s elevated plate voltage, the voltage between the sensor mounting points and the tube anode is higher than in the DX-2; this makes incorrect sensor positioning a more serious hazard.
11.3 Safe Discharge Procedure — DX-2SP (Elevated Voltage)
STEP 1 ── OPR switch to STBY; POWER switch to OFF.
│
STEP 2 ── UNPLUG ALL REAR-PANEL LEADS immediately:
Mains cord, antenna (RF IN / RF OUT), PTT/Key,
ALC cable, cooling air duct if external.
│
STEP 3 ── Wait MINIMUM 10 MINUTES.
DX-2SP HV filter bank (8× 470µF at elevated voltage)
is larger and slower to discharge than DX-2.
│
STEP 4 ── ANODE DISCHARGE TOOL:
10kΩ/25W resistor with insulated clip leads.
Clip one end to chassis; contact other end
firmly to GU84B (or FU-728F) anode cap.
Hold for 15 seconds. Visible corona = still live.
│
STEP 5 ── PLATE VOLTAGE MEASUREMENT:
Use 4,000V-rated DMM (Fluke 1000V + 10:1 probe
is NOT adequate for DX-2SP elevated voltage).
Confirm HV filter cap positive to chassis = <50V DC.
│
STEP 6 ── SCREEN SUPPLY (DUAL-POLARITY) MEASUREMENT:
Measure EG2 (blue wire) to chassis → <50V.
Also measure negative screen rail to chassis → >–50V.
Both rails must be confirmed discharged.
│
STEP 7 ── BIAS SUPPLY MEASUREMENT:
Measure –Eg1 (bias) to chassis → within –10V.
│
STEP 8 ── RE-VERIFY HV: confirm < 10V DC.
│
STEP 9 ── TEMPERATURE SENSOR CHECK:
Verify both sensors above tube are near-horizontal.
High voltage exists between sensors and tube anode.
│
STEP 10 ── SAFE: both rails < 10V DC. Work may begin.
Keep one hand behind back while probing.
Never defeat microswitch and apply mains simultaneously
with internal HV probing in progress.
Figure 1. DX-2SP safe discharge and verification procedure — includes dual-polarity screen rail confirmation unique to SP-family amplifiers.
11.4 Mains Earth Connection
A wing-nut earth connection is provided at the rear of the DX-2SP. The DX-2 manual states: “Connect this first, before making any other connection to the amplifier.” At the DX-2SP’s higher power levels, RF and safety earth bonding is more critical than in the DX-2; use a low-impedance earth strap of at minimum 6 mm² cross-section and the shortest practical length. Earth bond must be confirmed with a milliohm meter; a high-resistance earth connection is particularly dangerous at this amplifier’s power and voltage level.
12. RF Sensor — Forward Power Calibration at 2,000 W
The RF sensor (bi-directional coupler in a small metal box at the RF output) must be calibrated at the DX-2SP’s 2,000 W reference. Both the DX-2 and DX-3 manuals include an identical calibration table: “1500 W for DX-2 / 2000 W for DX-2SP / 3000 W for DX-3. Adjust potentiometer RF F for correct display indication.”7 A Bird 43 (or equivalent calibrated directional wattmeter) is required for this adjustment. Perform calibration on 20m into a 50 Ω dummy load; confirm the RF sensor forward power bargraph matches the reference wattmeter reading at 2,000 W. An incorrectly calibrated RF sensor will allow the SWR protection to trigger at the wrong threshold, either failing to protect the tube at high SWR or interrupting output unnecessarily.
13. QSK Module — Optional; Jennings TJ1A-26S Vacuum Relay
The DX-2SP QSK module was priced at US$100 as a factory-installed option. The Jennings TJ1A-26S vacuum relay, documented in the DX-2 schematic (section 16.9, “QSK v2 DX-2”), provides the antenna T/R switching for CW and digital modes. The no-hot-switching sequencing (output relay switches first, then RF drive is applied) is the same in the DX-2SP as in all Emtron QSK-equipped models.
The Jennings TJ1A-26S is rated for the RF power levels in the DX-2SP. At 2,000 W, verify the relay’s coil voltage is correct (24–26 V DC per the part number) and that the RF contacts show no silver erosion. A TJ1A-26S with arc-eroded contacts will cause RF power loss and reflection anomalies at the 2,000 W level before the contacts fully fail. Replacement relays: Jennings Technology (jenningsrelays.com) and RF Parts Co.
14. Display Board — LM3914 Bargraph Array
The DX-2SP Display Board is identical in architecture to the DX-2: eight LM3914 dot-mode bargraph ICs providing Ip (plate current), Vp (plate voltage), forward power, reflected power, Ig2+ (positive screen current), and Ig2− (negative screen current) channels. The Ig2− channel is particularly important on the DX-2SP, reflecting the dual-polarity screen supply’s ability to absorb reversed screen current. A persistently elevated Ig2− bargraph at rest (without RF drive) indicates a problem in the negative screen rail regulation. The LM3914 ICs are standard parts available from Mouser and DigiKey; replace individually if a specific bargraph column fails to illuminate or shows wrong-direction indication.
15. Cabinet, Finish & Assembly Hardware
The DX-2SP cabinet is built to the same standard as all Emtron DX models: 2 mm steel chassis with dark yellow chromate coating, 3 mm anodised aluminium front panel, and baked enamel texture finish in dark grey. The DX-2SP marketing confirms: “The finish is of high quality durable baked enamel texture paint and silk screening of a quality not found on any other similar equipment.” Despite this shared construction, the DX-2SP cabinet is noticeably heavier than the DX-2 due to the 4 kVA transformer; the difference is apparent when lifting the amplifier.
Item |
Notes |
|---|---|
Cabinet paint (baked enamel texture, dark grey)
Touch-up: Rust-Oleum Stops Rust Textured Spray; medium grey; test on underside first
|
The DX-2SP cabinet uses the same baked enamel textured finish as all DX models. Touch-up with Rust-Oleum Stops Rust Textured Spray in grey; apply in thin coats and allow full cure before reassembly. Heavier scratches on the 2 mm steel can be dressed with 400-grit wet-or-dry sandpaper followed by primer before texture coat. The higher weight of the DX-2SP means the cabinet is more susceptible to cosmetic damage from being set down hard on a bench; protect the cabinet bottom with neoprene feet during service. |
Front panel label / silk-screen (9-band legend)
3 mm anodised aluminium; silk-screened band positions; all 9 positions labelled including 12m and 10m
|
The DX-2SP front panel silk-screening shows all 9 band positions. Inspect the band switch knob indicator line for alignment with the panel legend; a misaligned knob sets the wrong band position, which at 2,000 W can cause severe mistuning and tube stress. If the knob indicator line is ambiguous, mark the 20m position with a fine-tip silver pen after confirming correct tank alignment, and use it as the reference for adjacent band positions. |
Power switch / Stby-Opr toggle
Front panel; DPDT or equivalent toggle; mains voltage across contacts; do not substitute lower-rated type
|
The mains ON/OFF switch must be rated for 250 VAC at 20 A or greater; at the DX-2SP’s higher power levels and 16 A mains draw, an under-rated replacement switch will overheat internally or arc across contacts. Use only switches with the original voltage and current ratings. The STBY/OPR toggle switch controls the screen voltage enable; it must have reliable break-before-make action to prevent momentary screen voltage application during switching transients. |
Rear panel connectors (SO-239 RF; RCA ALC; PTT)
RF input/output: SO-239 female; must handle 2,000 W RF; PL-259 connectors required at antenna
|
At 2,000 W RF output, the SO-239 output connector operates near the upper limit of standard UHF connectors. Verify the solder cup of the rear-panel SO-239 has no hairline cracks from past connector stress and that the centre pin is mechanically sound. A silver-plated SO-239 (not nickel-plated) is preferred at 2,000 W for minimum contact resistance. The mains IEC inlet must accept a cable rated for 20 A minimum (not a standard 10 A appliance cable); verify the cable rating matches the amplifier’s draw. |
Cabinet cover screws and top-cover alignment
Standard M4 pan-head; cover alignment determines safety microswitch engagement; inspect after any service
|
The DX-2SP cover uses the same M4 fasteners as the DX-2. When reassembling after service, verify all cover screws are in place and tightened before powering on; the safety microswitch’s activation depends on the cover seating correctly. A single missing cover screw near the microswitch location may allow the cover to sit slightly high, preventing proper microswitch activation and defeating the primary interlock. Verify microswitch operation after every service: with power off and cover fitted, apply mains; with cover removed, mains must be interrupted. |
Earth wing-nut and bonding strap
Rear panel; 6 mm² minimum strap; first connection before any other
|
The earth connection must be made before connecting any other lead. Inspect the wing-nut and its internal thread for corrosion; a high-resistance chassis earth on the DX-2SP at 2,000 W creates safety and RF performance problems simultaneously. Clean with contact cleaner; ensure a bright metal-to-metal contact. Verify the earth strap to station ground bus is minimum 6 mm² (for the DX-2SP’s higher fault current potential) and kept as short as physically possible. |
16. Parts Sources & Reference Documents
- emtrondv.com — Dan (former Emtron technician) — emtrondv.com — Version 7 AMPC control board (DX-2SP compatible); plate choke 1" OD × 6" long (stocked); limited spare modules; free technical advice; refurbished DX amplifiers (Sydney pickup). The definitive human resource for all DX-2SP technical queries including horizontal-board adjustment direction confirmation and FU-728F substitution specifics.
- Emtron DX-2 Operating Manual — Service Procedures Reference — manualslib.com / usermanual.wiki — Contains all shared modular service procedures (AMPC adjustments, soft-start, display board, HV supply), the forward power calibration table (2,000 W for DX-2SP), and the RF sensor adjustment procedure.
- Emtron DX-3 Operating Manual — AMPC Horizontal Board Confirmation — manualslib.com — Definitive reference for the DX-2SP horizontal AMPC board and counter-clockwise pot direction. Supersedes the DX-2 manual for this specific adjustment parameter.
- Emtron DX-3SP Operating Manual — DX-2SP Soft-Start Schematic — manualslib.com — Section 15.1 (Block Diagrams) includes the DX-2SP block diagram and the soft-start schematic showing BTA40-600B TRIAC, 4.7 nF Y2 safety capacitors, and 30 A fuses. Essential schematic reference for soft-start module service.
- GU84B / FU-728F Tube Sources — GU84B (NOS): DL3JJ / QRO-Shop (qro-shop.com), RF Parts Co. (rfparts.com); FU-728F (current production): Emtron direct (contact via emtrondv.com), DX Engineering (dxengineering.com) stocks Penta Laboratories FU-728F.
- Safety Capacitor Sourcing (Y2 and X2) — Mouser (mouser.com) and DigiKey (digikey.com); search for Class Y2 4.7 nF/250 VAC and Class X2 470 nF/250 VAC by Kemet, Vishay, or Wima. Verify IEC 60384-14 certification on the datasheet before purchase.
- BTA40-600B TRIAC — STMicroelectronics TO-220AC; Mouser part 511-BTA40-600B or equivalent. Verify STMicroelectronics origin; counterfeit devices with BTA40 markings are prevalent from grey-market suppliers and may have significantly lower actual current ratings.
- Jennings TJ1A-26S (QSK vacuum relay) — jenningsrelays.com; RF Parts Co.; Surplus City Liquidators. The 24 V coil model is the TJ1A-26S; verify coil voltage before ordering.
References & Footnotes
- Emtron DX-2SP marketing text, reproduced at Radioworld UK: “Besides the tube and a very special high voltage, high current band switch, as well as a 4 KVA mains transformer, the DX-2SP is identical to our DX-2.” radioworld.co.uk; also at eHam.net product page for Emtron DX-2SP: eham.net. ↩
- Emtron DX-3 Operating Manual (April 2005), Appendix 3: Adjustments. “If the protection wasn’t activated immediately, increase the sensitivity (Rotate clockwise for DX-1, DX-2 and anti-clockwise for DX-2SP and DX-3, which have horizontally installed boards — access on the component side).” manualslib.com. This passage also appears verbatim in the DX-3SP manual (February 2009): manualslib.com. ↩
- Emtron DX-2SP marketing: screen supply description. “Fully voltage regulated for +ve and −ve screen currents, combined with very effective current limiting … The protection against excessive screen current is so good, that we have tested the operation with full screen voltage, while the plate voltage was absent, for extended time, without damage to the tube.” radioworld.co.uk. ↩
- Emtron DX-2SP marketing: GU84B description. “Produced for the military, the SVETLANA GU-84B tube, with plate dissipation of 2500 watts … This 2500 watt plate dissipation tube has been constructed primarily for military communication, this tube is physically and electrically exceptionally rugged.” radioworld.co.uk. ↩
- WorldwideDX Radio Forum, May 2010. Post by Emtron distributor: “The all new range of Emtron Amplifiers are now using the FU-728F tetrode and using the Eimac 4CX1500B base so you can still use the older 4CX1500B in the same amp. You have to change the voltage on the power supply but the tap is included also.” worldwidedx.com. ↩
- Emtron DX-3SP Operating Manual (February 2009), Section 15.1 Block Diagrams. The DX-2SP block diagram (identified as “DX-2sp Block Diagram”) is included in the DX-3SP manual’s schematic section alongside the DX-3SP block diagram. The soft-start sub-schematic in Section 15.2 shows the BTA40-600B TRIAC, two 4.7 nF/250 VAC/Y2 safety capacitors, 470 nF/250 VAC/X2 and 220 nF/275 VAC/X2 capacitors, and two 30 A fuses; the same design applies to the DX-2SP. manualslib.com. ↩
- Emtron DX-2 Operating Manual, Section 15.1.2.4 — Forward Power calibration: “On 20m, operate the amplifier at the full nominal power, as indicated by an external power meter: 1500 W for DX-2 / 2000 W for DX-2SP / 3000 W for DX-3. Adjust potentiometer RF F for correct display indication.” manualslib.com; identical table in Emtron DX-3 Operating Manual, Section 17.2.4. ↩