Emtron DX-3 Linear Amplifier: Restoration & Service Guide

Emtron DX-3 Linear Amplifier:
Restoration & Service Guide

GU78B (4CX3000A) Tetrode • 3,000 W Carrier / 4,000 W PEP • 9 Bands 160m–10m incl. WARC • Dual-Fan Cooling • 700 µH Plate Choke • Horizontal AMPC Board • QSKv3 (Two Relay Options) • 60–90 W Drive • Transformer & RF Deck Shipped Separately • 43 kg Total • Emona Electronics Sydney

📝 VK6ADA Technical Papers 📅 March 2026 ⚡ 3,000 W carrier — GU78B / 4CX3000A 🇦🇺 Emona Electronics, Sydney (April 2005 manual) 🔄 9 Bands — 160m to 10m, all WARC ⚠ Extreme HV Hazard — Two-Person Installation
Abstract. The Emtron DX-3 is the single-tube 3,000 W HF linear amplifier at the apex of Emtron’s single-ended tetrode product line, powered by the GU78B (4CX3000A) — a ceramic-metal tetrode with a 2,500 W plate dissipation and a maximum anode voltage of 3,200 V DC. The DX-3 differs from the DX-2 family in five engineering-significant ways: the GU78B tube (a distinct physical and electrical design from the GU84B); dual-fan forced-air cooling (turbine blower mounted below the chassis pushing air upward through the tube, supplemented by a computer-type exhaust fan above the tube — unique in the Emtron range); a 700 µH plate choke (documented in the DX-3 RF module schematic 15.8, the highest inductance value in the series); a QSK Version 3 module (upgraded from the DX-2’s QSKv2, with two relay options documented: Jennings TJ1A-26S or P1D-1V); and a horizontally-mounted AMPC control board requiring the same counter-clockwise pot direction as the DX-2SP. The DX-3 manual (April 2005) is publicly available at ManualsLib and Internet Archive and contains complete schematics for all modules. The transformer ships separately from the RF deck in its own carton; both are required and two people are mandatory for installation. Total weight: 43 kg.
☠ Extreme Voltage Hazard — 3,200 V DC Capable

The DX-3 operates at a plate supply voltage appropriate for 3,000 W output from the GU78B, consistent with the tube’s 3,200 V DC maximum anode voltage. The DX-3 manual states in its CAUTION section: “The high voltages present inside the DX-3 are EXTREMELY DANGEROUS. Do not remove the top cover under any circumstances if any leads are still plugged into the rear of the amplifier — especially if the AC lead is plugged in the power outlet. Before any component inside the high voltage, power supply or output section is touched, unplug all rear panel leads and allow at least 5 minutes of ‘off time’. After that, you should further check this by momentarily shorting the tube anode to the chassis with a suitable insulated lead.”1

  • Disconnect all rear-panel leads before cover removal. Mains, RF, PTT, ALC, all cables.
  • Wait minimum 5 minutes; discharge GU78B anode to chassis via 10 kΩ/25 W insulated probe before any internal access.
  • Use a 4,000 V-rated DMM (or 5 kV-rated); confirm <50 V DC at HV bus before touching anything.
  • GU78B cathode heating time is 4 minutes minimum from cold; the tube must be warm before applying any plate voltage during service tests.
  • The transformer ships in a separate carton; it weighs 25 kg and requires two people for installation. Never attempt solo transformer installation.

1. The DX-3 in the Emtron Product Line — Top of the Single-Tube Range

The Emtron DX-3 (April 2005 operating manual) is the most powerful single-tube HF linear amplifier in the Emtron production line, exceeding the DX-2SP’s 2,000 W by a full kilowatt of continuous carrier power. Its 3,000 W carrier / 4,000 W PEP output is achieved with a single GU78B (4CX3000A) tetrode in the same desktop cabinet form factor as the DX-2 series. The DX-3’s internal view (Figure in Section 1.1 of the manual) shows the familiar Emtron layout — blower, QSK module, temperature sensor, RF sensor, RF choke, AMPC board, soft-start terminal block, HV power supply, safety microswitch, tank coil pair, and front-panel controls — but the scale of each component is noticeably larger than in the DX-2.2

Like all DX-3 amplifiers, the DX-3 includes QSK as standard equipment — not an option as in the DX-2 family. The manual states: “QSK is standard in all DX-3 amplifiers.” The EBS standing current is 0.75 A, higher than in the DX-2 / DX-2A (typically 0.5 A) reflecting the GU78B’s higher transconductance and different Class AB1 operating point.

⚠ Dan at emtrondv.com — Primary Service Resource: Dan spent over 20 years at Emtron building and testing approximately 1,000 amplifiers across the entire DX range including the DX-3. He offers Version 7 control boards (compatible with DX-3), plate choke (stocked — verify DX-3 700 µH type), limited spare modules, and free technical advice. Refurbished DX amplifiers available on local pickup from Sydney. emtrondv.com.

2. DX-3 vs DX-2 Family — Five Engineering Differences

DX-3 vs DX-2 Series — Service-Critical Differentiators
Feature
DX-2 / DX-2A
DX-2SP
DX-3
Final tube GU84B (4CX2500A) GU84B (early) / FU-728F (later) GU78B (4CX3000A) — completely different tube
Output power 1,500 W carrier 2,000 W carrier / 2,500 W PEP 3,000 W carrier / 4,000 W PEP
Heater voltage / current 27 V / 3.7 A 27 V / 3.7 A (GU84B) or 9 V (FU-728F) 27 V / 3.4–4 A (GU78B; similar voltage but different tube)
Cathode warm-up time 3 minutes (DX-2 manual) 3 minutes 4 minutes (240 seconds per GU78B datasheet)
Cooling One turbine blower One turbine blower Turbine blower below chassis + computer fan above tube (two fans)
Plate choke Standard DX-2 type Same as DX-2 700 µH (documented in RF module schematic 15.8)
QSK module version QSKv2 (DX-2 specific) QSKv2 QSKv3; two relay options: Jennings TJ1A-26S or P1D-1V
AMPC board orientation Vertical (CW = more sensitive) Horizontal (CCW = more sensitive) Horizontal (CCW = more sensitive; same as DX-2SP)
EBS standing current ~0.5 A typical ~0.5 A typical 0.75 A typical
Drive power 30–60 W 30–60 W 60–90 W
Mains fuses 2× 20 A 2× 30 A 2× 30 A
Transformer shipping Ships installed Ships installed (4 kVA) Transformer shipped separately; 25 kg; two-person install
Total weight ~20 kg ~30+ kg (4 kVA) 18 kg (RF deck) + 25 kg (transformer) = 43 kg
RF sensor calibration 1,500 W (DX-2) 2,000 W (DX-2SP) 3,000 W (VR1 / RF F)
Forward power RF F ref 1,500 W on 20m 2,000 W on 20m 3,000 W on 20m

3. DX-3 Technical Specifications

Output Power3,000 W carrier / up to 4,000 W PEP; all modes; all 9 bands
Frequency Coverage9 amateur HF bands: 1.8–2.0, 3.5–4.0, 7.0–7.5, 10.0–10.3, 14.0–14.35, 18.0–18.5, 21.0–21.5, 24.0–24.5, 28.5–29.99 MHz
Final TubeGU78B (= 4CX3000A); ceramic-metal tetrode; 2,500 W plate dissipation; 27 V / 3.4–4 A heater; 3,200 V DC max anode; transconductance 40–80 mA/V; rated to 250 MHz
Cathode Heating Time240 seconds (4 minutes) minimum per GU78B datasheet
Input Impedance50 Ω passive; VSWR 1.4:1 or less
Drive Power60–90 W nominal for full output
Output Impedance50 Ω passive; VSWR 2.6:1 or less
Distortion3rd order IM products >35 dB below rated output
Harmonic Output>50 dB below rated output
EBS Standing Current0.75 A typical (higher than DX-2’s 0.5 A)
Plate Choke700 µH (documented in RF module schematic 15.8)
CoolingTwo fans: (1) turbine blower below chassis pushing air upward through tube; (2) computer-type exhaust fan above tube; both two-speed, temperature-sensor controlled
QSK ModuleVersion 3 (QSKv3); standard equipment on all DX-3 amplifiers; Jennings TJ1A-26S or P1D-1V relay options; typical 3 ms switching time
AMPC BoardHorizontally mounted; counter-clockwise = increased protection sensitivity (same as DX-2SP)
Soft StartTDA1085C / TRIAC; 5-second ramp; X2/Y2 safety capacitors
Mains200–240 VAC; up to 30 A at 240 VAC; minimum 200 VAC
Mains Fuses2× 30 A normal-acting (rear panel)
Operating Temperature0 to 40° C ambient
RF Sensor Calibration3,000 W forward power (VR1 / RF F) on 20m
Display BoardLM3914 bargraph ICs; Ip, Vp, forward/reflected power, Ig2+, Ig2− (same architecture as DX-2)
RF Sub-ChassisGU78B on RF sub-chassis; tube connections below sub-chassis; same 9-way connector architecture as DX-2
Dimensions (RF Deck)435 mm W × 190 mm H × 465 mm D
WeightRF deck: 18 kg; Transformer (separate): 25 kg; Total: 43 kg
Transformer ShippingSeparate carton; must be installed by two people
Cabinet Finish2 mm steel; dark yellow chromate; 3 mm anodised aluminium front panel; baked enamel texture finish
FCC CertificationNot FCC-certified (DX-3 is for export/non-US markets; only Emtron amplifiers up to and including DX-2SP have FCC approval)
WarrantyFour years; full parts and labour except tube (tube: limited warranty)
ManufacturerEmtron Division of Emona Electronics Pty Ltd; 92–94 Wentworth Avenue, Sydney NSW 2010, Australia. Tel: +612 92110988; Fax: +612 92811508

4. GU78B Tetrode (4CX3000A) — Service Notes

The GU78B is a Soviet-origin ceramic-metal tetrode with a 2,500 W plate dissipation rating, primarily designed for military SSB and distributed-amplifier service up to 250 MHz. Its Western equivalent is the Eimac 4CX3000A. The GU78B is a significantly larger tube than the GU84B used in the DX-2 series: 111 mm maximum diameter versus the GU84B’s smaller body, and the GU78B uses an indirectly-heated oxide-coated cathode with a 4-minute (240-second) minimum warm-up time — one minute longer than the DX-2’s 3-minute requirement.3 The tube’s higher transconductance (40–80 mA/V, versus the GU84B’s lower value) enables the DX-3’s higher gain and power output with the same basic circuit architecture.

🔎 GU78B Key Service Parameters:
Heater: 27 V AC or DC / 3.4–4 A • Heater range: 25.5–28.3 V • Anode voltage: 3,200 V DC max / 6,200 V instantaneous • Grid 2 voltage: 300 V typical; 350 V max • Grid 2 dissipation: 30 W max • Cathode current max: 2,200 mA • Input capacitance: 100–150 pF • Mass: 1.8 kg • Maximum frequency: 250 MHz • Minimum cathode heating time: 240 seconds (4 minutes)

4.1 GU78B Bias Target & AMPC Adjustment

The DX-3’s bias target is set by the AMPC board POT3 (BIAS). Following the DX-3 manual Section 17.1.2 BIAS ADJUSTMENT procedure, the target is established during initial power-up with the EBS jumper removed. On a new or serviced DX-3, allow the GU78B minimum 4 minutes of heater warm-up before applying plate voltage; applying plate voltage to a cold GU78B risks cathode damage and significantly shortened tube life. The DX-3’s EBS standing current is 0.75 A (versus 0.5 A typical in DX-2 family), which must be confirmed after any bias adjustment.

⚠ 4-Minute GU78B Warm-Up — Mandatory: The GU78B datasheet specifies a minimum cathode heating time of 240 seconds. Apply mains; wait for READY LED; then wait an additional buffer beyond the READY indication before entering OPR for the first transmission. The DX-3’s READY timer is the minimum; do not rush into transmit immediately after READY on a cold amplifier.

4.2 GU78B Sourcing & NOS Gettering

The GU78B is available NOS (New Old Stock) from Eastern European military surplus suppliers and specialist tube dealers. NOS tubes should be gettered with heater-only operation (no plate or screen voltage) for a minimum of 12–16 hours before first applying plate voltage; the larger size of the GU78B relative to the GU84B means residual outgassing from the glass-to-ceramic seals may be marginally higher. Current-production GU78B or 4CX3000A from Penta Laboratories does not require gettering.

5. Dual-Fan Cooling — The DX-3’s Unique Architecture

The DX-3 is the only model in the single-tube Emtron range that uses a two-fan cooling architecture. The DX-3 internal view diagram (manual Section 1.1) shows both the turbine blower and the temperature sensor fan position. The manual describes: the turbine blower is positioned below the chassis, pushing air upward through the GU78B’s cooling fins from below; a computer-type fan is positioned above the tube, sucking the hot exhaust air away from the tube body. Both fans operate at two speeds, controlled by the temperature sensor system.

This dual-fan arrangement is necessary because the GU78B’s 2,500 W plate dissipation at 3,000 W output generates thermal energy that a single turbine blower cannot exhaust fast enough for sustained operation at full power. The DX-3 manual states its 3,000 W carrier power output is supported for continuous commercial-type duty cycles. Any DX-3 that has had the upper computer-type fan removed, disconnected, or its duct obstructed will operate in a degraded thermal condition that shortens GU78B life and risks thermal cut-out activation during sustained operation.

Dual-Fan System — Service Notes
Component
Service Notes
BLOWER (turbine; below chassis) Commercial-grade turbine blower; forced air upward through GU78B fins Two-speed; temperature-controlled; same type as DX-2 blower but may have higher flow rating; Category A for exact spare
The primary turbine blower in the DX-3 is mounted below the chassis and forces cooling air upward through the GU78B’s ceramic cooling fins from the base. A failed primary blower must be detected immediately; the DX-3 will activate temperature cut-off quickly at 3,000 W without cooling airflow. Both fan speeds must work correctly: low speed for idle/standby; high speed during sustained transmit. Verify both speed levels by listening to blower pitch; the transition from low to high should be audible when the amplifier is keyed. Fan bearing noise (persistent growling or clicking) indicates imminent bearing failure; replace proactively. Contact Dan at emtrondv.com for the correct DX-3 turbine specification; the DX-3 blower may have a higher airflow rating than the DX-2’s.
FAN (computer type; above tube) Exhaust computer fan; positioned above GU78B; sucks hot air away from tube Two-speed; temperature-controlled; standard 80mm or 92mm computer fan; critical for GU78B longevity
The upper computer-type fan is unique to the DX-3 in the Emtron range. It removes exhaust heat from the tube area immediately above the GU78B’s anode radiator. Verify the fan is present, connected, and rotating freely before any operational test. A failed upper fan at 3,000 W will cause the temperature sensors above the tube to indicate over-temperature within minutes; the DX-3 will self-protect by cutting to bypass. The fan is a standard computer-type unit (80 mm or 92 mm; 12 V DC); verify the correct diameter and CFM rating before substituting. The replacement must operate at two speeds under temperature sensor control, not at a single fixed speed.
TEMPERATURE SENSORS (×2) Two sensors above GU78B; fan speed control and over-temperature protection Near-horizontal orientation mandatory; high voltage between sensors and tube anode; same sensor type as DX-2
Same positioning requirements as DX-2: the sensors must remain near-horizontal above the tube. The DX-3 manual repeats the warning from the DX-2 manual about sensor positioning. After servicing the GU78B or the upper computer fan, verify both sensor positions before any power-on test. High voltage exists between sensor mounting points and the tube anode; a sensor pushed down into contact with the tube body can create a shock hazard as well as causing incorrect temperature readings.

6. RF Deck — GU78B RF Module & 700 µH Plate Choke

6.1 RF Module Schematic Notes — “R1 Changed to 680 Ω”

The DX-3 RF module schematic (Section 15.8 of the DX-3 manual, ManualsLib page 30) carries an important service note at its heading: “R1 changed to 680 Ω.” This indicates a documented production change to the RF module circuit during the DX-3’s production life. R1 is a resistor in the RF module whose original value was changed to 680 Ω during production; the note is a service advisory that any DX-3 entering service should have R1 at 680 Ω. If a DX-3 was manufactured before this change and has not been updated, or if R1 has been replaced with the original value during a past repair, the RF module is not in the current specification.4

⚠ R1 = 680 Ω — Verify on Every DX-3 RF Deck Service: Before performing any RF deck work on the DX-3, visually confirm R1 reads 680 Ω (or measure in circuit). If R1 measures a significantly different value (original value may have been 100 Ω or another value), bring it to the current specification before returning the amplifier to service. The note in the schematic applies to all production DX-3 amplifiers.

6.2 700 µH Plate Choke

The DX-3 RF module schematic (15.8) documents a 700 µH plate choke. This is a notably higher inductance than the plate choke in the DX-1 and DX-2 series, which is specified at approximately 700 µH in the DX-3 manual. Dan at emtrondv.com stocks the plate choke (1” OD × 6” long); when ordering for a DX-3, verify the correct inductance specification. The choke must provide adequate impedance at 160 m (1.8 MHz) while not presenting a series resonance on any of the nine operating bands. A damaged or incorrectly valued plate choke in the DX-3 is more consequential than in the DX-2 due to the higher plate voltage and operating current.

RF Deck — Commonly Replaced Components
Component
Service Notes
L-CHOKE (700 µH plate choke) RF plate choke; 700 µH per DX-3 schematic 15.8 1” OD × 6” long; Dan stocks; higher inductance than DX-2 choke; must be free of series resonance on all 9 bands; ceramic cylinder available separately
The 700 µH plate choke is the RF plate supply feed. At the DX-3’s higher plate voltage and operating current, a cracked or arced choke represents a more severe failure than in smaller amplifiers. Inspect the winding for carbonization, cracked turns, or burn marks. After any arc event inside the RF deck, the plate choke is the first item to inspect. Replacement from Dan at emtrondv.com; specify DX-3 application and confirm the 700 µH specification. The ceramic cylinder is available separately if the winding itself is intact but the former is cracked.
C-BYPASS (4× 1,000 pF / 6 kV) Plate bypass capacitors at RF sub-chassis base Same as DX-2 RF module circuit; high SRF required; replace as set of 4 after arc events
The DX-3 RF module schematic shows 4× 1,000 pF/6 kV plate bypass capacitors, same configuration as the DX-2. At the DX-3’s higher plate voltage, any bypass capacitor with a reduced voltage rating from prior flashover stress must be replaced. Replace as a complete set of four to ensure matched characteristics. Use Vishay/Vitramon or equivalent high-voltage high-SRF ceramic disc types; verify SRF exceeds 50 MHz.
A106 DIODES (5× in DX-3; per schematic) A106 clamping diodes in screen/protection circuit 5 diodes in DX-3 schematic 15.8 (fewer than DX-2’s 7; different protection topology); 140 V clamp
The DX-3 RF module schematic (15.8) shows 5 A106 clamping diodes in the screen/protection circuit, consistent with the DX-3’s different RF module topology compared to the DX-2’s 7 A106 diodes. After any flashover event, inspect all 5 A106 diodes; a conducting-in-reverse A106 will clamp the screen voltage below operating level. Replace any failed A106 devices as a complete set from the same manufacturing batch to ensure consistent forward voltage drops and clamping characteristics.
C (10 nF / 1 kV; RF module) Screen bypass capacitor in RF module; higher value than DX-2 10 nF / 1 kV (per DX-3 schematic 15.8); DX-2 uses 2.2 nF at same node; GU78B requires larger screen bypass at this location
The DX-3 RF module uses 10 nF/1 kV at the screen bypass position, a significantly higher value than the DX-2’s 2.2 nF. This reflects the GU78B’s different input capacitance and screen bypass requirements. If this capacitor is replaced with a DX-2 value (2.2 nF) in error, the screen supply will be inadequately bypassed at lower HF frequencies, causing instability on 160m and 80m. Verify capacitor value before installation; use a 10 nF / 1 kV ceramic disc type with adequate voltage rating.
S-BAND (9-position ceramic switch) All 9 positions active; higher current rating than DX-2 due to 3,000 W output Category A — unavailable; inspect for arc tracks at all 9 positions; higher voltage stress at 10m/12m at 3,000 W
Category A — Unavailable from Dan. The DX-3 band switch is under higher electrical stress than any DX-2-family switch due to the 3,000 W power level. Inspect all 9 wafer positions for arc tracking and carbon deposits using a 10× magnifier with strong LED illumination. Carbon tracks at the 10m position (highest RF voltage across switch wafers) are particularly common on heavily-used DX-3 amplifiers. Clean with DeoxIT D5 followed by 99% isopropyl alcohol; allow full evaporation. A donor DX-3 must be sourced for band switch replacement.
C-PLATE / C-LOAD (variable air capacitors; 6:1) Tune and Load air variables; must handle 3,000 W RF peak voltage Category A — unavailable; 6:1 reduction drives essential at 3,000 W; inspect air gap for arc damage at minimum-C end
Category A — Unavailable from Dan. The variable capacitors in the DX-3 must withstand significantly higher RF peak voltages than the DX-2 equivalents due to the combination of higher plate voltage and 3,000 W output. Inspect both capacitors for bent plates, arc damage, and bearing wear in the reduction drives. The 10m and 12m positions (minimum Plate capacitance) experience the highest electric field stress; arc damage at minimum-C position is the most common variable capacitor failure on high-hours DX-3 units.
MOV (140 V; screen circuit protection) Metal Oxide Varistor in screen protection chain 140 V clamp; per DX-3 schematic 15.8; check after any screen fault or flashover event; also 3-stage MOV flash-over protection per manual
The DX-3 manual specifies: “a 3-stage protection circuit using extremely fast MOVs protects the screen regulator from the dangerous plate voltage in case of a flash-over in the tube.” After any tube flashover event, inspect all MOV devices in the screen protection chain for physical damage, cracking, or thermal deformation. A failed MOV may pass leakage current continuously, dragging the screen voltage down or up depending on failure mode. Replace with certified Littelfuse or Bourns MOV devices at the correct voltage rating.

7. AMPC Control Board — Horizontal Orientation, Counter-Clockwise Pots

The DX-3’s AMPC control board is mounted horizontally, as confirmed by the DX-3 operating manual (April 2005), Appendix 3: Adjustments: “Rotate clockwise for DX-1, DX-2 and anti-clockwise for DX-2SP and DX-3, which have horizontally installed boards — access on the component side.” 5 The DX-3 and DX-2SP are the only single-tube Emtron amplifiers with this horizontal orientation. The pot direction is identical to the DX-2SP: counter-clockwise increases protection sensitivity (tighter trip threshold).

AMPC Board — DX-3 Adjustment Reference
Pot / Label
DX-3 Notes (horizontal board; counter-clockwise = more sensitive)
POT3 / BIAS
GU78B idle current target: set per DX-3 manual Section 17.1.2. EBS jumper must be removed during adjustment (EBS OFF position). Counter-clockwise reduces current (horizontal board). After any GU78B replacement, perform full BIAS and PRE-BIAS adjustment sequence before any transmission.
POT2 / SCREEN
Screen voltage adjustment; measure at EG2 (blue wire) in READY/OPR per DX-3 manual Section 17.1.5. In the DX-3, it is noted: “in DX-3 it is easier to measure on either side of R18.” Do not exceed 350 V GU78B G2 max. Required after tube or control board replacement.
POT6 / IPTRIP
IPTRIP sensitivity adjustment. Use 140 Ω/130 Ω SWR jig (2.7:1 threshold). Counter-clockwise increases sensitivity (tighter trip) for horizontal board. Verify on 20m at nominal 3,000 W. Protection should trip at 140 Ω; must not trip at 130 Ω.
POT4 / EBS
EBS threshold adjustment; sets the input drive level at which EBS activates and plate current jumps from pre-bias to full operating current. Perform on 20m into dummy load. EBS jumper in ON position during this adjustment. Same procedure as DX-2.
POT7 / PRE-BIAS
EBS pre-bias current; small idle current that flows when EBS is active (no modulation). Prevents “harsh sound at beginning of each word” per DX-3 manual. Counter-clockwise direction on horizontal board.
POT1 / IG2LIMIT
Factory-set screen current limit; do not adjust. The DX-3 manual Section 17.1.6 notes this potentiometer has been factory-adjusted and should not be changed without a milliammeter in series with the screen supply. GU78B G2 dissipation max: 30 W.
VR6 / IG2+; VR5 / IG2−
Screen current bargraph display calibration (Display Board). The DX-3 manual documents both adjustments separately for the first time in the Emtron DX range (Section 17.2.5). Ig2−: set VR5 to middle position. Ig2+: connect a milliammeter in series with the screen supply (EG2 pin to blue screen wire) and adjust VR6 for correct bargraph indication.

8. QSK Version 3 Module — Two Relay Options

The DX-3 uses the QSKv3 module, documented in the DX-3 manual as schematic 15.7 (QSKv3 DX-3, document number QSKV3DX3, dated Monday 7 January 2002). The QSKv3 differs from the DX-2’s QSKv2 in one specifically documented circuit difference: the DX-3 QSK schematic identifies two relay options: the Jennings TJ1A-26S (used in all earlier Emtron QSK modules) or the P1D-1V (a different vacuum relay type). The QSKv3 schematic shows both relay types as alternatives.6

The P1D-1V is a single-pole double-throw (SPDT) vacuum relay. If a DX-3 has been fitted with a P1D-1V rather than the Jennings TJ1A-26S, obtain the P1D-1V coil voltage specification before ordering a replacement; the relay designations indicate different coil voltages may exist in the P1D family. The QSKv3 circuit uses the same coil drive components (R3 = 100/1 W, R1 = 33/2 W, C1 = 47 µF/50 V, C2 = 10 µF/50 V, 1N4004 diodes throughout).

QSKv3 Module — Service Notes
Component
Service Notes
RL2 (Jennings TJ1A-26S or P1D-1V) QSK antenna switching relay; two relay options in DX-3 QSKv3 First: identify which relay is fitted before ordering replacement; Jennings TJ1A-26S or P1D-1V; check coil voltage carefully for P1D variants
Before ordering a replacement, physically identify which relay is fitted in the DX-3. The Jennings TJ1A-26S is a cylindrical glass-body vacuum relay with the characteristic Jennings bayonet mount; the P1D-1V is a different physical form. If the fitted relay is a TJ1A-26S, replacement from Jennings Technology or RF Parts Co. is straightforward. If the fitted relay is a P1D-1V, verify the coil voltage from the existing relay marking before ordering. At 3,000 W, the relay contacts must be intact; verify RF contact cleanliness and switching action (no-hot-switching must be confirmed by observing relay-first, then RF drive sequencing as documented in the DX-3 manual QSK waveform, Section 16.1).
C1 (47 µF / 50 V) and C2 (10 µF / 50 V) QSK coil driver timing and energy-storage capacitors Electrolytic; check for ESR increase / capacitance loss after 10+ years of service
The 47 µF and 10 µF electrolytic capacitors in the QSK module determine the coil drive timing and energy storage for relay pull-in. ESR increase with age is the primary failure mode; a high-ESR C1 causes slow relay pull-in or failure to pull in reliably under load, manifesting as intermittent QSK action or hot-switching RF into the relay contacts. Measure ESR in-circuit with an LCR meter; replace both as a pair if ESR exceeds 1 Ω on the 47 µF or 2 Ω on the 10 µF.
R3 (100 Ω / 1 W) and R1 (33 Ω / 2 W) QSK coil current limiting resistors Non-inductive; check for drift after overload events; R1 = 33/2W must handle relay coil current
These resistors limit relay coil current and protect the drive circuit. A failed-open R3 or R1 will prevent relay pull-in entirely. Check resistance with an ohmmeter; R3 should read 100 Ω (±5%) and R1 should read 33 Ω (±5%). Replace with non-inductive carbon or metal-film resistors at the specified wattage; use wirewound types only if clearly non-inductive.

9. HV Power Supply & Transformer

The DX-3’s transformer ships in a separate carton from the RF deck. The DX-3 manual Section 3.3 and Section 4.2 both address this. The transformer weighs 25 kg and the manual warns: “Two people are needed to install the transformer. The best is to put the DX-3 on a flat, smooth surface such as a bench or table top, covered by a small carpet of a folded blanket, so that it can be moved by sliding.” At 30 A from the 240 VAC mains during 3,000 W operation, the transformer primaries must be wired for the correct mains voltage (200, 220, 230, or 240 VAC) before first power-on; an incorrect primary tap risks overloading the HV secondary.

HV Supply — Commonly Replaced Components
Component
Service Notes
C-HV (main HV filter bank) HV filter electrolytic capacitors; supplies plate voltage for 3,000 W operation Higher voltage / current stress than DX-2; replace as matched bank; verify equalising resistors intact; 105°C-rated types recommended
The DX-3 HV filter capacitor bank is under greater stress than the DX-2 due to the combination of higher plate voltage and higher supply current. Replace all capacitors as a matched bank (same manufacturer, batch, and date code) to ensure equal voltage sharing in the series string. Verify the HV equalising resistors across each capacitor section are all intact and of equal value before installing the replacement bank. Use 105°C-rated electrolytics throughout. Cap bank failure in the DX-3 with a sub-optimal bank produces unequal voltage distribution and accelerated ageing of whichever capacitor is sharing the highest voltage.
D-HV (HV rectifier bridge) HV rectifier diode strings; full-wave bridge Series strings must have total PIV rating ≥2× DX-3 plate voltage; higher voltage than DX-2 requires higher PIV
The DX-3 HV rectifier bridge must have a total PIV rating comfortably exceeding the higher plate supply voltage used in the DX-3. Series strings of 1N4007 (or equivalent 1 kV) diodes with equalising resistors are the standard Emtron construction. At the DX-3’s operating voltage, 6× 1N4007 per leg (6,000 V PIV) provides adequate margin. Replace diode strings as complete units after any HV fault; never replace individual diodes from a series string.
R (25 Ω / 50 W in HV B+ line) Flash-over protection resistor in HV B+ supply Non-inductive wirewound; limits fault current during tube flash-over; mentioned in DX-3 specs as “25 ohm, 50 watt resistor”
The DX-3 technical specifications state: “a 25 ohm, 50 watt resistor in the high voltage B+ circuit and MOV devices in the screen circuit further protects the tube and the power supply from a possible tube internal flash-over.” After any flashover event, test this resistor first. It will show elevated resistance or open circuit if the fault current was sufficient. Replace with a non-inductive wirewound 25 Ω/50 W type; do not use inductive wirewound types in this position.

10. Safety Systems — Cover Interlock, Discharge & Safety Capacitors

10.1 Cover Safety Microswitch

The DX-3 cover safety microswitch is the primary electrical interlock. The DX-3 manual Appendix 3 notes: “Most of the following adjustments require the amplifier to be open and powered up. This also implies defeating the mains interlock safety switch, which is extremely dangerous since high voltage / high power DC and AC and RF voltages are exposed.” The microswitch must open (break mains continuity) when the cover is removed. Verify after every cover-related service action. Never return a DX-3 to operational service with a defeated or failed microswitch.

10.2 Safe Discharge Procedure

  STEP 1 ── STBY switch; POWER switch to OFF.
               │
  STEP 2 ── DISCONNECT ALL REAR-PANEL LEADS:
            Mains cord, RF IN, RF OUT, PTT/Key,
            ALC cable. Any other control cables.
               │
  STEP 3 ── Wait MINIMUM 5 MINUTES.
            DX-3 HV filter bank at elevated plate voltage.
            Larger bank than DX-2; allow full discharge time.
               │
  STEP 4 ── ANODE DISCHARGE TOOL:
            10kΩ/25W resistor on insulated clip lead.
            Clip one end to chassis.
            Contact firmly to GU78B anode cap.
            Hold for 15 seconds. Watch for spark = still live.
               │
  STEP 5 ── HV MEASUREMENT (5kV-rated DMM preferred):
            Confirm HV filter cap positive to chassis < 50V DC.
            Note: DX-3 plate voltage may exceed 3,000V DC;
            ensure meter is rated for actual voltage present.
               │
  STEP 6 ── SCREEN SUPPLY:
            Measure EG2 (blue wire) or either side of R18
            (in DX-3, R18 is the easier measurement point)
            to chassis → < 50V.
               │
  STEP 7 ── BIAS SUPPLY:
            Measure –Eg1 to chassis → within –10V.
               │
  STEP 8 ── RE-VERIFY HV: < 10V DC.
               │
  STEP 9 ── TEMPERATURE SENSORS:
            Verify both sensors above GU78B are near-horizontal.
               │
  STEP 10 ── SAFE. Work may begin.
             Keep one hand behind back while probing.
             Never defeat microswitch and apply mains
             while simultaneously probing HV circuits.

Figure 1. DX-3 safe discharge and verification procedure. Note R18 as the preferred EG2 screen voltage measurement point in the DX-3.

10.3 Safety Capacitors — X2 and Y2 in Soft-Start Module

The DX-3 soft-start schematic (Section 15.6) is identical to the DX-2’s and shows the same safety capacitor requirements. All three capacitor classes are confirmed in the DX-3 schematic.

Soft-Start Safety Capacitors — Mandatory Certified Replacements
Component / Ref
Value & Class
Position
Replacement Requirement
C13, C14 (Y2 pair) 4.7 nF / 250 VAC / Class Y2 Line-to-chassis IEC 60384-14 Class Y2 mandatory. Kemet, Vishay, EPCOS, or equivalent. Standard ceramic discs prohibited.
X2 cap (470 nF) 470 nF / 250 VAC / Class X2 Line-to-neutral IEC 60384-14 Class X2 mandatory. Must withstand mains transients without violent failure. Standard MKT film prohibited.
C2 / X2 cap (220 nF) 220 nF / 250 VAC / Class X2 Across mains switch Class X2 at 250 VAC minimum. Same sourcing requirement as 470 nF X2. Kemet, Vishay, or Wima.

11. Troubleshooting Reference — DX-3 Fault Table

The DX-3 manual (Section 12) provides a comprehensive troubleshooting guide. The following table summarises key fault symptoms from the manual with the most probable cause and first-action service response for each:

Fault Diagnosis Reference
Symptom / LED Indication
Most Probable Cause & First Action
No power; no display Check mains cable, wall outlet, rear-panel fuses (2× 30 A), and cover microswitch engagement. The DX-3 transformer ships separately; verify it has been installed and wired for correct primary voltage.
Fan not working The DX-3 has two fans (turbine below chassis; computer fan above tube). Identify which fan has failed. A failed upper fan may not be immediately obvious from listening; check by visual inspection with cover removed (after safe discharge). A failed lower turbine is obvious from absence of airflow noise.
FAULT LED on Over-current, over-temperature, or screen fault. Isolate by checking plate current bargraph (over-current), temperature sensor position and fan operation (over-temperature), or Ig2 bargraph behaviour (screen fault). The FAULT LED replaces several possible fault sources; systematic isolation is required.
READY LED never illuminates C7 (tantalum timer cap) on AMPC board. Dan’s procedure applies identically to DX-3: check pin T110 (yellow wire) voltage; if >1 V after 4 minutes (allowing for GU78B’s longer warm-up), C7 is the prime suspect. Replace with tantalum type. If C7 replacement does not resolve, replace U5 (LMC555).
Ig2 bargraph blinks fast; no plate voltage Manual Section 12.6: Ig2 blinking without plate voltage indicates the screen is alive but plate voltage is absent. Check HV power supply, HV rectifier bridge, and transformer secondary connections. A failed HV bleeder resistor or open rectifier leg can produce this symptom.
Sparks / discharges in RF area Manual Section 12.7: arcs inside the RF section. Most common causes: carbon track on band switch wafers (especially 10m position); cracked variable capacitor plate; damaged or incorrectly-valued plate choke; high dust contamination in the RF section. Clean RF section with dry compressed air and inspect all RF components before any re-energisation.
SWR cut-off (SWR LED) Antenna SWR exceeds 2.6:1. Verify antenna system; check RF sensor calibration (VR3 / RF R for reflected power, VR1 / RF F for forward power); verify SWR protection threshold adjustment (IPTRIP / POT6, remembering counter-clockwise = more sensitive on horizontal board).
Frequent overdrive cut-off Input drive exceeds the DX-3’s linearity limit (60–90 W nominal). The DX-3 requires more drive than the DX-2; verify transceiver output is in the 60–90 W range, not higher. Use ALC (Section 10.2 of manual) to limit maximum drive power.
Low output power; no other fault indication Check GU78B emission (tube may need replacement after extensive service); verify bias is correctly set (POT3 with EBS jumper removed); check 700 µH plate choke integrity; verify R1 = 680 Ω (production change note on RF module schematic); check variable capacitor alignment on all bands.

12. Cabinet, Front Panel & Assembly Hardware

The DX-3 cabinet is built to the same specifications as other DX models: 2 mm steel chassis, dark yellow chromate, 3 mm anodised aluminium front panel, baked enamel texture finish. Cabinet dimensions: 435 mm W × 190 mm H × 465 mm D (slightly deeper than the DX-2 at 465 mm vs 465 mm).

The DX-3 front panel displays all 9 band positions on the band switch knob legend. The Tune and Load controls, Power/Stby-Opr switches, and all bargraph indicators are on the front panel as in other DX models. The DX-3 does not have an analogue meter for plate current; the manual states the design is “greatly simplified by the absence of meter switching, mechanical display and front panel level setting controls” — all indication is via the LED bargraph array. This means a failed LM3914 bargraph IC on the display board leaves the operator with no plate current or power indication.

Cabinet & Hardware — DX-3 Specific Notes
Item
Notes
Transformer installation (25 kg; separate carton) Two people mandatory; slide on blanket-covered surface; set primary tap before first power-on
The DX-3 transformer is shipped in its own separate carton for safety in transit; its 25 kg mass would be damaging to the RF deck if the two were shipped together. Follow the DX-3 manual Section 3.3 installation procedure: put the DX-3 RF deck on a smooth blanket-covered surface to allow sliding; two people install the transformer from above into its mounting rails. Verify the transformer primary tap is correctly set for local mains voltage (200, 220, 230, or 240 VAC) before connecting the mains lead. An incorrect tap will result in either elevated HV (dangerous) or reduced output power.
Mains fuses (2× 30 A; rear panel) Same fuse rating as DX-2SP; do not substitute 20 A; ceramic 30 A IEC type
The DX-3 uses 2× 30 A normal-acting fuses on the rear panel, the same as the DX-2SP and significantly higher than the DX-2’s 20 A. Never install 20 A fuses in a DX-3; they will blow under sustained 3,000 W operation. Use only ceramic 30 A fuses of the type and size specified in the manual.
Mains earth connection (wing-nut; rear panel) Connect first before any other lead; 6 mm² minimum earth strap to station RF earth
At 3,000 W output, the earth bonding of the DX-3 is critical for both RF safety and EMC. Use a minimum 6 mm² earth strap of the shortest possible length to the station RF earth busbar. Verify the wing-nut makes clean metal-to-metal contact with the chassis; apply contact cleaner and wire-brush if tarnished. A high-resistance earth at 3,000 W can cause RF interference problems and creates a shock hazard.
Cabinet paint (baked enamel; dark grey texture) Touch-up: Rust-Oleum Stops Rust Textured Spray; test on underside first
Same cabinet finish as all DX models. Touch-up with Rust-Oleum Stops Rust Textured Spray in grey. At 43 kg total weight, the DX-3 is vulnerable to cosmetic damage when moved; the transformer installation procedure specifically uses a blanket-covered surface to prevent cabinet scratching. Inspect the ventilation openings on the bottom (for the turbine blower inlet) and the top/sides (for the exhaust fan outlet) for obstruction; blocked ventilation at 3,000 W causes rapid temperature cut-off.
RF connectors (SO-239 IN/OUT; rear panel) Must handle 3,000 W RF; silver-plated SO-239 recommended; PL-259 connectors must be VHF-rated
The DX-3 manual requires: “The use of a high quality RG-8A/U, RG-213 or similar 50 ohm coaxial cable line terminated with a ‘VHF’ type PL-259 connector is essential.” At 3,000 W, standard UHF connectors are at or beyond their rated limits; use silver-plated SO-239 connectors and solid-machined silver-plated PL-259 types rated for 1.5 kW or greater. Inspect the SO-239 output connector for cracking and silver wear after any period of high-duty-cycle operation.

13. Parts Sources & Reference Documents

  • Emtron DX-3 Operating Manual (April 2005)manualslib.com — Complete schematics including RF module (15.8), QSK v3 (15.7), soft-start (15.6), HV supply (15.2), and control board (15.9). The primary service reference for all DX-3 work. Also available as full text at archive.org.
  • emtrondv.com — Danemtrondv.com — Version 7 AMPC control board (DX-3 compatible); plate choke 1” OD × 6” long (stocked; verify 700 µH DX-3 specification); free technical advice; refurbished DX amplifiers (pickup Sydney). The definitive human resource for all DX-3 technical queries.
  • GU78B Datasheetok1rr.com/tubes/gu78b.pdf — Heater 27 V / 3.4–4 A; plate dissipation 2,500 W; 3,200 V DC max anode; grid 2 max 350 V; cathode heating time 240 seconds; input capacitance 100–150 pF; transconductance 40–80 mA/V.
  • GU78B / 4CX3000A Tube Sources — NOS GU78B: Eastern European and Ukrainian surplus dealers on eBay (hfvhfparts and similar verified high-feedback sellers); confirm “new old stock, untested” and allow 12–16 hours heater-only gettering. Current production 4CX3000A: Penta Laboratories (pentalabs.com); stockists via RF Parts Co. (rfparts.com).
  • Safety Capacitors (Y2 and X2) — Mouser (mouser.com), DigiKey (digikey.com); Kemet, Vishay, or Wima certified Class Y2 (4.7 nF/250 VAC) and X2 (470 nF and 220 nF / 250 VAC). Verify IEC 60384-14 certification on each datasheet.
  • Jennings TJ1A-26S / P1D-1V (QSK relays) — TJ1A-26S: Jennings Technology (jenningsrelays.com), RF Parts Co. P1D-1V: verify coil voltage from existing relay marking; specialty vacuum relay suppliers or surplus sources. Confirm coil voltage before ordering.
  • LM3914, LMC555, TDA1085C, TIPL760A, M4-12H — All standard parts from Mouser or DigiKey; same specifications and replacement procedures as documented for DX-2 series.

References & Footnotes

  1. Emtron DX-3 Operating Manual (April 2005), CAUTION section (page 1 of the manual). Direct quotation of the safety warning that precedes all operational content. manualslib.com.
  2. Emtron DX-3 Operating Manual (April 2005), Section 1 General Description. “The Emtron DX-3 Linear Amplifier is a 3000 watt average output power, for the 160m through 10m amateur bands (9 bands) … It utilises a single high performance tetrode, type GU78B (4CX3000A), a ceramic metal tube with a plate dissipation of 2500W. … QSK is standard in all DX-3 amplifiers.” Also: EBS standing current 0.75 A. Section 2, Technical Specifications. manualslib.com.
  3. GU-78B Tetrode Datasheet, OK1RR tube archive. Cathode: indirectly heated, oxide-coated. Heater: 27 V / 3.4–4 A. Cathode heating time: 240 seconds. Maximum anode voltage DC: 3,200 V. Maximum grid-2 voltage: 350 V. Plate dissipation: 2,500 W. Input capacitance: 100–150 pF. Transconductance: 40–80 mA/V. ok1rr.com/tubes/gu78b.pdf.
  4. Emtron DX-3 Operating Manual (April 2005), Section 15.8 Circuit Diagram RF Module. Schematic heading note: “R1 changed to 680 ohm.” This production change note is the authoritative reference confirming R1 = 680 Ω in the current DX-3 RF module specification. manualslib.com.
  5. Emtron DX-3 Operating Manual (April 2005), Appendix 3: Adjustments. “If the protection wasn’t activated immediately, increase the sensitivity (Rotate clockwise for DX-1, DX-2 and anti-clockwise for DX-2SP and DX-3, which have horizontally installed boards — access on the component side).” manualslib.com. This is the definitive authoritative citation for the horizontal board direction.
  6. Emtron DX-3 Operating Manual (April 2005), Section 15.7 Circuit Diagram QSK. Schematic document number QSKV3DX3; titled “QSKv3 DX-3”; dates Monday 7 January 2002. Relay legend shows both: “Jenings TJ1A-26S Or P1D-1V”. Component values: C1 = 47 µF/50 V; C2 = 10 µF/50 V; R3 = 100/1 W; R1 = 33/2 W; all diodes 1N4004. manualslib.com.
✍ Mike Peace VK6ADA  /  r-390a.net Administrator vk6ada.com.au  —  Vintage Radio Restoration Technical Series